1 General
BU 0200 en-US-4920
29
Pos : 47 /Anl eitungen/ Elek tronik/FU und Start er/ 1. Allgemei nes/Z ulas sungen/U L und C SA Zul ass ung_T eil 1 [allgem ei n] @ 7\mod_1432204309954_14638. docx @ 221459 @ 3 @ 1
1.6.1 UL and CSA approval
File No. E171342
The categorization of protective devices approved by the UL according to United States Standards for
the devices described in this manual is listed below with essentially the original wording. Please refer
to the section "Electrical Data" in this manual for the categorization of individually relevant fuses or
circuit breakers.
All devices are equipped with motor overload protection.
(
Section 7.2 "Electrical data")
Pos : 48 /Anl eitungen/ Elek tronik/FU und Start er/ 1. Allgemei nes/Z ulas sungen/U L und C SA Zul ass ung_T eil 2_Ergänz ung - Gruppenabsic herung [ SK 2xx E, SK 1xx E, -FD S] @ 7\m od_1433943179219_14638. docx @ 223861 @ @ 1
Information
Group fuse protection
The devices can be protected as a group via a common fuse (details below). Adhere to total current
specifications and use correct cables and cable cross-sections when doing this. If the device/devices
is/are being installed close to the motor, this also applies to the motor cable.
Pos : 49 /Anl eitungen/ Elek tronik/FU und Start er/ 1. Allgemei nes/Z ulas sungen/U L und C SA Zul ass ung_T eil 2_Ergänz ung [SK 1xx E, SK 2xxE, SK 5xx E, -FDS, 5x xP] @ 7\mod_1433943883212_14638.docx @ 223893 @ 5 @ 1
UL/CSA conditions according to the report
Pos : 50 /Anl eitungen/ Elek tronik/FU und Start er/ 1. Allgemei nes/Z ulas sungen/U L und C SA Zul ass ung_T eil 3_original_W ortlaut [ SK 2xx E] @ 6\m od_1427210838785_0. doc x @ 209532 @ @ 1
Information
"Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection
must be provided in accordance with manufacturer instructions, the National Electric Code and any additional
local codes."
“Use 80°C Copper Conductors Only." (size 1 – 3)
“Use 60/75°C copper field wiring conductors.” (size 4)
„These products are intended for use in a pollution degree 2 environment“
“The device has to be mounted according to the manufacturer instructions.”
“For NFPA79 applications only”
Содержание NORDAC FLEX SK 2 E-111-123-A Series
Страница 1: ...BU 0200 en US NORDAC FLEX SK 200E SK 235E Users Manual for Frequency Inverters...
Страница 5: ...Publisher BU 0200 en US 4920 5...
Страница 283: ...Key word index BU 0200 en US 4920 283...
Страница 284: ...6072003 4920...