NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
186
BU 0200 en-US-4920
Pos : 474 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P400- P499/Param et er P480... P481 – Verw endung der Merk er @ 6\mod_1422968583767_14638.docx @ 201098 @ @ 1
P480 … P481
Using Marker
With the aid of the two flags it is possible to define simple, logical sequences of functions.
To do this, the "triggers" for a function (e.g. a motor PTC overtemperature warning) are defined in
parameter (P481) in arrays [-09] - "Flag 1" and [-10] - "Flag 2".
In arrays [-11] and [-12] of parameter P480, the function which the variable frequency drive is to
perform if the “trigger” is active is assigned in arrays [-11] and [-12] of parameter P480. I.e.
parameter P480 determines the response of the variable frequency drive.
Example:
In an application, the variable frequency drive is to reduce the actual speed immediately (e.g. with
an active fixed frequency) if the motor is in the overtemperature range (“Motor overtemp.PTC”).
This is to be implemented by "Deactivation of analog input 1" via which in this example, the actual
setpoint is normally set.
This is used to reduce the load on the motor, so that the temperature can stabilize or the drive
unit reduces speed to a defined value before a shut-down due to error occurs.
Step
Description
Function
1
Determine the trigger,
Set flag 1 to the "Motor overtemperature warning"
function
P481 [-07]
Function "12"
2
Specify the reaction,
Set flag 1 to the function "Setpoint 1 On/Off”
P480 [-09]
Function "19"
Depending on the function which is selected in (P481) the function may need to be inverted by
modification of the standardization (P482).
Pos : 475 /Allgem ein/ Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0. doc x @ 2265496 @ @ 1
Pos : 476 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P400- P499/Param et er P482 – Normi erung Bus I/O O ut Bits [SK 1x 0E, SK 2xx E, SK 2xx E-FDS] @ 2\m od_1346931812166_14638.docx @ 42956 @ @ 1
P482
[-01]
...
[-10]
Standard BusIO Out Bits
(standardization of Bus I/O Out Bits)
S
-400 … 400 %
{ all 100 }
Adjustment of the limit values of the bus Out bits. For a negative value, the output function will be
output negative.
Once the limit value is reached and positive values are delivered, the output produces a High
signal, for negative setting values a Low signal.
[-01] =
Bus / AS-i Dig Out1
(Bus IO Out Bit 0 + AS-i 1)
[-02] =
Bus / AS-i Dig Out2
(Bus IO Out Bit 1 + AS-i 2)
[-03] =
Bus / AS-i Dig Out3
(Bus IO Out Bit 2 + AS-i 3)
[-04] =
Bus / AS-i Dig Out4
(Bus IO Out Bit 3 + AS-i 4)
[-05] =
Bus / IOE Dig Out1
(Bus IO Out Bit 4 + DO 1 of the
first
SK xU4-IOE (DigOut 02))
[-06] =
Bus / IOE Dig Out2
(Bus IO Out Bit 5 + DO 2 of the
first
SK xU4-IOE (DigOut 03))
[-07] =
Bus/ 2nd IOE Dig Out1
(Flag 1 + DO 1 of the
second
SK xU4-IOE (DigOut 04))
[-08] =
Bus / 2nd IOE Dig Out2
(Flag 2 + DO 2 of the
second
SK xU4-IOE (DigOut 05))
[-09] =
BUS statusword Bit 10
[-10] =
BUS statusword Bit 13
Pos : 477 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P400- P499/Param et er P483 – Hyst erese Bus I/O O ut Bits [SK 1x 0E, SK 2xx E, SK 2xx E-FDS] @ 2\m od_1346931812868_14638.docx @ 42980 @ @ 1
P483
[-01]
...
[-10]
Hyst. BusIO Out Bits
(Hysteresis Bus I/O Out Bits)
S
1 … 100 %
Difference between switch-on and switch-off point to prevent oscillation of the output signal.