NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
166
BU 0200 en-US-4920
Pos : 424 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ P4xx St euerklemm en @ 0\m od_1327678262854_14638.docx @ 14962 @ 3 @ 1
5.2.5 Control terminals
Parameter
{factory setting}
Setting value/description/note
Supervisor
Parameter
set
Pos : 425 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P400- P499/Param et er P400 – Fkt . Sollwer tei ngang [SK 2x 0E] @ 2\mod_1346931795708_14638.docx @ 42330 @ @ 1
P400
[-01]
...
[-09]
Setpoint I/P Funct.
(input setpoint functions)
SK 2x0E
P
0 ... 36
{ [-01] = 1 }
{ [-02] = 0 }
{ [-03] = 0 }
{ [-04] = 0 }
{ [-05] = 1 }
{ [-06] = 0 }
{ [-07] = 1 }
{ [-08] = 0 }
{ [-09] = 0 }
SK 2x0E size 1 … 3
SK 2x0E size 4
[-01]
Analog input 1
, function of analog input 1 integrated into the VFD
[-02]
Analog input 2
, function of analog input 2 integrated into the VFD
[-03]
External analog input 1
, AIN1 of the first I/O extension (SK xU4-IOE)
[-04]
External analog input 2
, AIN2 of the first I/O extension (SK xU4-IOE)
[-05]
Setpoint module
[-06]
Digital input 2
, can be set to pulse signal
evaluation via P420 [-02] =26 or 27. The
pulses can then be evaluated in the VFD as
an analog signal according to the function set
here.
[-06] Potentiometer 1
, function of
potentiometer P1 integrated into
the VFD. DIP switches 4/5 must
be "off" so that the function can be
affected by this parameter setting
(chapter 4.3.2.2)
[-07]
Digital input 3
, can be set to pulse signal
evaluation via P420 [-03] =26 or 27. The
pulses can then be evaluated in the VFD as
an analog signal according to the function set
here.
[-07] Potentiometer 2
, same as
potentiometer 1
[-08]
External
analog in.
1 2nd IOE,
"External analog input 1 2nd IOE"
, AIN1 of the second
I/O extension (SK xU4-IOE) (= analog input 3)
[-09]
External
analog in.
2 2nd IOE,
"External analog input 2 2nd IOE"
, AIN2 of the second
I/O extension (SK xU4-IOE) (= analog input 4)
... Setting values below
Pos : 426 /Allgem ein/ Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0. doc x @ 2265496 @ @ 1
Pos : 427 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P400- P499/Param et er P400 – Fkt . Sollwer tei ngang [SK 2x 5E] @ 2\mod_1346931796285_14638.docx @ 42355 @ @ 1
P400
[-01]
...
[-09]
Setpoint I/P Funct
(input setpoint functions)
SK 2x5E
P
0 ... 36
{ [-01] = 1 }
{ [-02] = 15 }
{ [-03] = 0 }
{ [-04] = 0 }
{ [-05] = 1 }
{ [-06] = 0 }
{ [-07] = 1 }
{ [-08] = 0 }
{ [-09] = 0 }
[-01] Potentiometer 1
, function of potentiometer P1 integrated into the VFD. DIP switches 4/5
must be "off" so that the function can be affected by this parameter setting (chapter 4.3.2.2)
[-02] Potentiometer 2
, same as potentiometer 1
[-03] External analog input 1
, AIN1 of the first I/O extension (SK xU4-IOE)
[-04] External analog input 2
, AIN2 of the first I/O extension (SK xU4-IOE)
[-05] Setpoint module
[-06] Digital input 2
, can be set to pulse signal evaluation via parameter P420 [-02] =26 or 27.
The pulses can then be evaluated in the VFD as an analog signal according to the function
set here.
[-07] Digital input 3
, can be set to pulse signal evaluation via parameter P420 [-03] =26 or 27.
The pulses can then be evaluated in the VFD as an analog signal according to the function
set here.
[-08] Ext.
AI
1 2.IOE,
"External analog input 1 2nd IOE"
, AIN1 of the second I/O extension
(SK xU4-IOE) (= analog input 3)
[-09] Ext.
analog in.
2 2nd IOE
,
"External analog input 2 2nd IOE"
, AIN2 of the second I/O
extension (SK xU4-IOE) (= analog input 4)
The basic versions of SK 2x5E devices do not have an analog input. An analog function can only
be used by using options (array [-01]...[-05] and [-08]…[-09]) or using digital input 2 or 3 (array [-
06]...[-07]).
... Setting values below
Pos : 428 /Allgem ein/ Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0. doc x @ 2265496 @ @ 1