5 Parameter
BU 0200 en-US-4920
193
Pos : 503 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P515 – CAN- Adr ess e_01 [ SK 1x 0E, SK 2x xE, SK 2xx E-FDS] @ 2\mod_1346932167813_14638.docx @ 43172 @ @ 1
P515
[-01]
...
[-03]
CAN bus address
(CAN address (system bus))
S
0 ... 255
dec
{ all 32
dec
}
or { all 20
hex
}
Setting of the systembus address.
[-01] =
Slave address
, Receive address for system bus
[-02] =
Broadcast slave address
, system bus reception address (slave)
[-03] =
Master address,
"Broadcast master address"
,
transmission address for system bus
(master)
NOTE:
If up to four VFD are to be linked via the system bus, the addresses must be set as follows VFD 1
= 32, VFD 2 = 34, VFD 3 = 36, VFD 4 = 38.
Pos : 504 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P515 – CAN- Adr ess e_02 [ SK 1x 0E, SK 2x xE] @ 17\m od_1490096962359_14638. docx @ 2336235 @ @ 1
The system bus addresses should be set via DIP switches (chapter 4.3.2.2).
Pos : 505 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P516 – Aus blendfrequenz 1 @ 0\mod_1328092606664_14638. docx @ 15057 @ @ 1
P516
Skip frequency 1
(skip frequency 1)
S
P
0.0 ... 400.0 Hz
{ 0.0 }
The output frequency around the frequency value (P517) set here is not shown.
This range is transmitted with the set brake and acceleration ramp; it cannot be continuously
supplied to the output. Frequencies below the absolute minimum frequency should not be set.
0.0 =
Skip frequency inactive
Pos : 506 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P517 – Aus blendbereic h 1 @ 0\mod_1328092662665_14638. doc x @ 15058 @ @ 1
P517
Skip frequency area 1
(skip frequency range 1)
S
P
0.0 ... 50.0 Hz
{ 2.0 }
Skip range for the >Skip frequency 1< P516. This frequency value is added and subtracted from
the skip frequency.
Skip frequency area 1: P516 - P517 ... P516 + P517
Pos : 507 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P518 – Aus blendfrequenz 2 @ 0\mod_1328092706493_14638. docx @ 15059 @ @ 1
P518
Skip frequency 2
(skip frequency 2)
S
P
0.0 ... 400.0 Hz
{ 0.0 }
The output frequency around the frequency value (P519) set here is not shown.
This range is transmitted with the set brake and acceleration ramp; it cannot be continuously
supplied to the output. Frequencies below the absolute minimum frequency should not be set.
0.0 =
Skip frequency inactive
Pos : 508 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P519 – Aus blendbereic h 2 @ 0\mod_1328092748353_14638. doc x @ 15060 @ @ 1
P519
Skip frequency area 2
(skip frequency range 2)
S
P
0.0 ... 50.0 Hz
{ 2.0 }
Skip range for the >Skip frequency 2< P518. This frequency value is added and subtracted from
the skip frequency.
Skip frequency area 2: P518 - P519 ... P518 + P519
Pos : 509 /Allgem ein/ Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0. doc x @ 2265496 @ @ 1