5 Parameter
BU 0200 en-US-4920
147
Pos : 330 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P100- P199/Param et er P113 – Tippfr equenz [ SK 1x 0E, SK 2xx E] @ 2\m od_1346931600084_14638.docx @ 42206 @ @ 1
P113
Jog frequency
(jog frequency)
S
P
-400.0 ... 400.0 Hz
{ 0.0 }
When using the
Simple Box or Parameter Box
to control the VFD, the jog frequency is the initial
value following successful enabling.
Alternatively, jog frequency can be activated via one of the digital inputs when control is via the
control terminals.
The jog frequency setting can be entered directly via this parameter or, if the VFD is enabled via
the keyboard, by pressing the OK key. In this case, the prevailing output frequency is set in
parameter P113 and is then available for the next start.
NOTE:
Specified setpoints via the control terminals, e.g. jog frequency, fixed frequencies or
analog setpoints, are generally added with the correct sign. The maximum frequency set (P105)
cannot be exceeded and the minimum frequency (P104) cannot be undershot.
Pos : 331 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P100- P199/Param et er P114 – Lüf tzei t Br ems e @ 0\mod_1327587947470_14638.docx @ 14910 @ @ 1
P114
Brake delay off
(brake release time)
S
P
0 ... 2.50 s
{ 0.00 }
Electromagnetic brakes have a physically induced delayed reaction time during release. This can
lead to the motor running while the brake is still applied, which will cause the inverter to
malfunction with an overcurrent report.
This release time can be taken into account in parameter P114 (brake control).
The VFD supplies the set absolute minimum frequency (P505) during the adjustable release time,
thus preventing movement against the brake.
See also parameter P107 >Brake application time< (setting example).
NOTE:
If the brake release time is set to 0, then P107 is the brake release and application time.
Pos : 332 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P100- P199/Param et er P120 – O pti ons überw ac hung [ SK 1x 0E, SK 2x xE, SK 54xE, SK 2xx E-FDS] @ 2\mod_1346931600646_14638.docx @ 42231 @ @ 1
P120
[-01]
...
[-04]
Ext Control Units
(option monitoring)
S
0 ... 2
{ 1 }
Monitoring of communication at system bus level (in case of fault: fault message 10.9)
Array levels:
[-01] =
TB bus (extension 1)
[-02] =
2nd IOE (extension 2)
[-03] =
1st IOE (extension 3)
[-04] =
extension 4
Setting values:
0 =
Monitoring off
1 =
Auto
, communication is only monitored if an existing communication is interrupted. If a
module that was previously present is not found after switching on line power, this does
not result in a fault.
Monitoring only becomes active when one of the extensions starts communication with the
device.
2 =
Control now active
"Monitoring immediately active"
,
the VFD starts monitoring the
corresponding module immediately after switching on line power. If the module is not
detected when line power is switched on, the VFD remains in the "not ready for switch-on"
state for 5 seconds and then triggers an error.
.
Note:
If even fault messages that are detected by the optional module (e.g. faults at field bus level)
do not lead to a shutdown of the drive electronics, set parameter (P513) to the value {-0.1} as well.
Pos : 333 /Allgem ein/ Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0. doc x @ 2265496 @ @ 1
Содержание NORDAC FLEX SK 2 E-111-123-A Series
Страница 1: ...BU 0200 en US NORDAC FLEX SK 200E SK 235E Users Manual for Frequency Inverters...
Страница 5: ...Publisher BU 0200 en US 4920 5...
Страница 283: ...Key word index BU 0200 en US 4920 283...
Страница 284: ...6072003 4920...