P536
Current limit
(current limit)
S
0.1 ... 2.0/2.1
(x nominal VFD
current)
{ 1.5 }
The VFD output current is limited to the set value. If this limit value is reached, the VFD reduces
the actual output frequency.
With the analog input function in P400 = 13/14, this limit value can also be varied and cause an
error message (E12.4).
0.1 ... 2.0 =
Multiplier
with the VFD nominal current, gives the limit value.
2.1 =
OFF
means that this limit value is disabled. The VFD supplies the maximum possible
current.
Pos : 532 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P500- P599/Param et er P537 – Puls abs chalt ung @ 0\mod_1328093709635_14638. docx @ 15075 @ @ 1
P537
Pulse disconnection
(pulse disconnection)
S
10 ... 200 %/201
{ 150 }
This function prevents rapid shutdown of the VFD according to the load. With the pulse switch-off
enabled, the output current is limited to the set value. This limitation is implemented by brief
switching off of individual output stage transistors, the actual output frequency remains
unchanged.
10...200% =
Limit value in relation to nominal VFD current
201 =
The function is
so to speak
disabled
, the VFD supplies the maximum
possible current. However, at the current limit the pulse switch off can still be
active.
NOTE:
The value set here can be undershot by a smaller value in P536.
At smaller output frequencies (<4.5 Hz) or higher pulse frequencies (>6 kHz or
8 kHz, P504) the pulse switch-off can be undershot by the power reduction (
8.5).(please see chapter 8.4 "Reduced output power")
NOTE:
If the pulse switch-off is disabled (P537=201) and a high pulse frequency is
selected in parameter P504, the VFD automatically reduces the pulse
frequency when the power limit is reached. If the load on the VFD is reduced
again, the pulse frequency increases back to the original value.
Pos : 533 /Allgem ein/ Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0. doc x @ 2265496 @ @ 1
Содержание NORDAC FLEX SK 2 E-111-123-A Series
Страница 1: ...BU 0200 en US NORDAC FLEX SK 200E SK 235E Users Manual for Frequency Inverters...
Страница 5: ...Publisher BU 0200 en US 4920 5...
Страница 283: ...Key word index BU 0200 en US 4920 283...
Страница 284: ...6072003 4920...