BU 0200 en-US-4920
Pos : 310 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P100- P199/Param et er P103 – Br emsz eit @ 0\mod_1327574939362_14638. doc x @ 14899 @ @ 1
P103
Deceleration time
(deceleration time)
P
0 ... 320.00 s
{ 2.00 }
Deceleration time the time corresponding to the linear frequency reduction from the set maximum
frequency to 0 Hz (P105). If a prevailing setpoint of <100% is used, the deceleration time
decreases accordingly.
Deceleration time can be extended by certain circumstances such as the selected >Switch-off
mode< (P108) or >Ramp rounding-off< (P106).
NOTE:
Make sure parameter values are realistic. A setting of P103 = 0 is not permissible for drive units!
Notes on ramp gradient:
see parameter (P102)
Pos : 311 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P100- P199/Param et er P104 – Minim ale Fr equenz @ 0\mod_1327575009471_14638.docx @ 14900 @ @ 1
P104
Minimum frequency
(minimum frequency)
P
0.0 ... 400.0 Hz
{ 0.0 }
The minimum frequency is the frequency supplied by the VFD as soon as it is enabled and no
additional setpoint is set.
These are added to the set minimum frequency in combination with other setpoints (e.g. analog
setpoint or fixed frequencies).
This frequency is not reached when
a. the drive is accelerated from standstill.
b. the VFD is blocked. The frequency then decreases to the absolute minimum frequency
(P505) before it is blocked.
c. the VFD reverses. The rotating field reverses at the absolute minimum frequency (P505).
This frequency can be continuously not reached if the "Maintain Frequency" function (digital input
function = 9) is executed during acceleration or braking.
Pos : 312 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P100- P199/Param et er P105 – Maxim ale Frequenz [SK 1x0E, SK 2xx E, SK 2x xE-FD S] @ 58\mod_1606120603956_14638.docx @ 2694758 @ @ 1
P105
Maximum frequency
(maximum frequency)
P
0.1 ... 400.0 Hz
{ 50.0 }
The frequency supplied by the VFD after being enabled and once the maximum setpoint is
present, e.g. analog setpoint corresponding to P403, an appropriate fixed frequency or maximum
via the Simple Box/Parameter Box.
This frequency can only be exceeded through slip compensation (P212), the "Maintain the freq."
function (digital input function = 9) or switching to another parameter set with a lower maximum
frequency.
Maximum frequencies are subject to certain restrictions, e.g.
•
restrictions in the field weakening mode,
•
compliance with mechanically permissible speeds,
•
PMSM: maximum frequency restricted to a value that is slightly above the rated frequency.
This value is calculated from the motor data and the input voltage.
Pos : 313 /Anleit ungen/El ektr onik /FU und St art er/5. Par ameter/ Par ameter auflist ung (P000 .. .)/P100- P199/Param et er P105 – Maxim ale Frequenz _Ergänz ung_Di p [SK 2xx E] @ 9\mod_1448032265888_14638. docx @ 265398 @ @ 1
{ 50.0 } DIP7 = off
{ 60.0 } DIP7 = on
(chapter 4.3.2.2)
Pos : 314 /Allgem ein/ Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0. doc x @ 2265496 @ @ 1
Содержание NORDAC FLEX SK 2 E-111-123-A Series
Страница 1: ...BU 0200 en US NORDAC FLEX SK 200E SK 235E Users Manual for Frequency Inverters...
Страница 5: ...Publisher BU 0200 en US 4920 5...
Страница 283: ...Key word index BU 0200 en US 4920 283...
Страница 284: ...6072003 4920...