NORDAC FLEX (SK 200E ... SK 235E) – Users Manual for Frequency Inverters
224
BU 0200 en-US-4920
Diagnostic LEDs
LED
Signal
Name
Color
Description
Status
Meaning
DOUT 1
yellow Digital output 1
on
High signal applied
DIN 1
yellow Digital input 1
on
High signal applied
DIN 2
yellow Digital input 2
on
High signal applied
DIN 3
yellow Digital input 3
on
High signal applied
DIN 4
yellow Digital input 4
on
High signal applied
TEMP
yellow Motor PTC
thermistor
on
Motor overtemperature
CHOP
yellow Brake chopper
on
Brake chopper active, brightness → degree of load
(only
SK 2x5E)
BRAKE
yellow Mech. Brake
on
Mech. Brake released
DOUT 2
yellow Digital output 2
on
High signal present
(only SK 2x0E)
BUS-S
green
System bus
off
No process data communication
Status
Flashing
(4 Hz)
"BUS Warning"
On
Process data communication active
Receipt of at least 1 telegram/s
SDO data transfer is not indicated
BUS-E
red
System bus
off
No error
Error
Flashing
(4 Hz)
Monitoring error P120 or P513
E10.0/E10.9
Flashing
(1 Hz)
Error in an external system bus module
Bus module
Timeout on external BUS (E10.2)
System bus module has module error (E10.3)
on
System bus in state "BUS off"
Pos : 654 /Allgem ein/ Allgem eingültig e Module/---------Seitenumbr uc h k ompakt --------- @ 13\m od_1476369695906_0. doc x @ 2265496 @ @ 1
Содержание NORDAC FLEX SK 2 E-111-123-A Series
Страница 1: ...BU 0200 en US NORDAC FLEX SK 200E SK 235E Users Manual for Frequency Inverters...
Страница 5: ...Publisher BU 0200 en US 4920 5...
Страница 283: ...Key word index BU 0200 en US 4920 283...
Страница 284: ...6072003 4920...