P R O G R A M M I N G
NESS D16 (V4.6) CONTROL PANEL - INSTALLER MANUAL
1E 2E 3E 4E 5E 6E 7E 8E
ON = Factory default setting.
Enable T
est Calls
Mains R
epor
t delay
Listen-in to diallerSwinger shutdownLine F
ault Monitor
Line F
ault to A
UX2
.
.
OPTION No
DESCRIPTION
P89E
Miscellaneous Reporting options
ON ON
ON
ENABLE TEST CALLS
This option enables the reporting of dialler test calls to the Central station.
PROGRAMMING SEQUENCE:
P89E 1E
toggles the option ON and OFF
P89E 1E OFF: No Test Calls
P89E 1E ON:
Test Calls enabled
P89E 1E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
ON: Test Calls enabled
NOTES:
• RELATED OPTIONS:
P83E
Test Call Interval
P84E
Time before next Test call
MAINS REPORT DELAY
This option allows Mains Fail reports to be delayed by one hour if the mains
power has been off continuously for that time. Normally, the Mains Fail report is
sent immediately the power fails.
PROGRAMMING SEQUENCE:
P89E 2E
toggles the option ON and OFF
P89E 2E OFF: Mains Fail reports immediately
P89E 2E ON:
Mains Fail report is delayed by 1 hour
P89E 2E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
ON: Mains Fail report is delayed
NOTES:
LISTEN-IN TO DIALLER
This is a diagnostic feature for installers. Listen-In is turned on for a minimum of
4 minutes after exiting Program Mode.
During Listen-In, the dialler message and other telephone tones can be heard
through the Siren output (at low volume) while the dialler is sending reports.
The 4-minute period is restarted whenever any key on the keypad is pressed.
To turn Listen-In off, go back into Installer Program mode and toggle the option
OFF.
PROGRAMMING SEQUENCE:
P89E 3E
toggles the option ON and OFF
P89E 3E OFF: No Listen-In
P89E 3E ON:
Listen-In enabled
P89E 3E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
OFF: No Listen-In
NOTES:
• For convenient and private Listen-In,
temporarily connect a spare horn
speaker to the Siren output.