NESS D16 (V4.6) CONTROL PANEL - INSTALLER MANUAL
RADIO DEVICES - OPERATION
ALARM:
Any Ness Radio Device can operates on any zone 1-16 as programmed by
P101E~P116E. The hardwired zones 1-16 continue to operate in parallel. (Radio Keys can
operate on radio zones 1~16 for special purposes, but are normally programmed to
operate as Radio Codes. See page 56).
KEYSWITCH INPUT:
A Radio Device programmed to Zone 8 will still work as an alarm even
if the Zone 8 input operation has been changed to Keyswitch operation. The P60E 2E and
3E options only affect the Zone 8 terminal inputs.
VIBRATION:
Radio device zone signals IGNORE the P30E-P38E vibration sensor settings.
TAMPER REPORT:
Radio Device Tamper operation depends on the Armed State of the
control panel.
RADIO TAMPER:
causes the keypad to continuously beep and also to flash the RADIO,
TAMPER and the ZONE (identifying the detector) lights. Pressing any key on the keypad or
sending a TAMPER RESTORE will clear this warning.
LOW BATTERY REPORT:
A low battery gives 10 beeps and flashes the RADIO & the
BATTERY light. The ZONE light identifying the radio device is also ON. The flashing lights
stop when any key on the keypad is pressed or a detector code with no low battery is
received. Low Battery generates HISTORY and DIALLER reports ONCE only (until the low
battery is fixed and a restore report is received).
SUPERVISION:
If a zone has the P65E option ON and a radio code has been programmed
for that zone, then the supervision is active. This means that the radio detector does not
need to have its SUPER enabled (via header link) for the SUPERVISED timeout to occur.
(Useful as an inactivity alarm). A zone supervision failure always flashes the identifying
ZONE light and the RADIO light.
RK1 RADIO KEY
PENDANT
100-665
RK3 RADIO KEY
3 BUTTON
RK4 RADIO KEY
4 BUTTON
100-664
100-067
R15
RADIO PIR
100-663
RR1 RADIO
REED SWITCH
100-662
RSM RADIO
SMOKE DETECTOR
100-203
SIGNAL
TYPE
NESS RADIO DEVICES
Signal types transmitted
ALARM
OFF button
OFF button
PANIC button
PANIC button
yes
yes
yes
yes
PANIC button
yes
yes
yes
yes
yes
yes
yes
yes
yes
ON button
ON button
yes
yes
yes
RESTORAL
LOW BATT
PANIC
TAMPER
SUPERVISION
O
FF
O
N
PANIC
RADIO SUPERVISION
The purpose of Radio Supervision is to verify the correct operation of Ness
Radio PIRs. The Supervision signal from the Radio PIR tells the panel that the
device has not been removed from radio range and is in working order.
Non-SUPERVISION Radio PIRs can also be programmed and used with the
D16 SUPERVISION TIMERS.
A non-SUPERVISION enabled Radio PIR will transmit signals to the D16 only
when it has detected an event. Obviously, there is no guaranteed signal period.
In either case, when the allowed time limit is exceeded then a WARNING is first
given (if programmed by P66E 3E), and then after 1 minute, the programmed
RADIO SUPERVISION ALERTS are generated by the D16.
NOTE: Manually Excluding a Supervised Zone will also disable Radio
Supervision for that zone.