P R O G R A M M I N G
NESS D16 (V4.6) CONTROL PANEL - INSTALLER MANUAL
DAY ZONES
Day Zones operate when the panel is fully disarmed, i.e. when Area 1, Area 2
and Monitor are all off. When alarmed, these zones will activate the assigned
outputs instantly.
The outputs mapped to the Day Zone will turn on while the zone is unsealed.
Turn P64E 2E on, to limit Day Zone alarms to 2 seconds.
PROGRAMMING SEQUENCE:
P53E [Zone No]E
toggles the options ON and OFF
P53E [Zone No]E OFF: The zone is not a Day zone
P53E [Zone No]E ON: The zone is a Day zone
P53E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
all OFF: No Day zones
NOTES:
• RELATED OPTIONS:
P63E 5E-8E
Day zone output mapping
P64E 2E
Brief Day Mode alarm
• TYPICAL USES: Instant alert when a
delivery door is opened, doorway alert for
a shop.
24hr ZONES
24hr Zones operate at all times regardless of the mode of panel operation, i.e.
Armed, Disarmed or Monitor. When alarmed, these zones will activate
assigned outputs immediately. To reset those alarms a valid user code must
be entered.
Selecting a zone as 24hr will override any other zone type setting such as
Instant, Delayed or Handover.
PROGRAMMING SEQUENCE:
P52E [Zone No]E
toggles the options ON and OFF
P52E [Zone No]E OFF: The zone is not a 24hr zone
P52E [Zone No]E ON: The zone is a 24hr zone
P52E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
all OFF: No 24hr zones
NOTES:
• The Tamper input is always a 24hr zone
• For silent 24hr zones, deselect the zone/s from options
P54E-P57E (Reset, Strobe, Sonalert & Siren)
• To change a 24hr zone to any other zone type, the zone
must also be re-assigned to an AREA (P45E or P46E).
• 24hr zones are independent of Area operation. All other
zone types must be assigned to at least one Area to
become active.
TEMPORARY DAY ZONES
D16 Version 4.6 introduces the ‘Temporary
Day Zone’ feature which allows easy and
flexible Day Zone selection and operation.
While remaining in normal operating mode,
the user can add and remove ‘Temporary
Day Zones’ and enable/disable day zone
operation using simple key strokes.
TO ENABLE TEMPORARY DAY ZONES
To enable Temporary Day Zone selection
and operation, the Brief Day Alarm feature
(installer option P64E 2E) must be ON. If
P64E 2E is OFF, the Temporary Day Zone
feature will be unavailable but Permanent
Day Zones will still operate and will sound
the programmed output while the zone is
unsealed.
P64E 2E is OFF by default.
USER COMMANDS (In normal Operat-
ing Mode).
+
Selection Mode. Enter
P
followed by
E
when in operating mode to enter
Temporary Day Zone selection mode.
[Zone No.]
+
Zone Selection. To select or deselect zones
to be Temporary Day Zones. The selected
zones are indicated by the corresponding
zone number.
Permanent Day Zones, (set by installer
option P53E), are not displayed in selection
mode. Permanent Day Zones can be
selected as Temporary Day Zones but this
has no effect as those zones are already
day zones.
Saves changes and returns to normal
operating mode.
+
Enables and Disables Day Mode. This
enables/disables both Temporary and
Permanent Day Zones.
When Day Mode is enabled, any unsealed
day zone will sound the programmed
output for 2 seconds. When Day Mode is
disabled, an unsealed day zone will simply
be indicated on the keypad as an unsealed
zone. (Note: The keypad does not indicate
if Day Mode is enabled or disabled).
AUX 2 OPTION
When the Temporary Day Zone feature is
enabled, the installer option P63E 6E selects
Aux 2 output instead of the strobe output.
This allows a remote warning device such
as a buzzer to be connected for day zone
warning. This may be needed if an
additional audible day zone warning is
needed, although the keypad sonalert,
(P63E 7E), is more than adequate in most
cases.
RELATED OPTIONS
P64E 2E
, Brief Day Alarm. Turn this option
on to enable Temporary Day Zones.
Factory default = OFF.
P63E 5E
, Day Mode to Reset output.
P63E 6E
, Day Mode to Strobe output.
If P64E 2E is ON, then this option sends
day alarms to the AUX 2 output.
P63E 7E
, Day Mode to Sonalert.
P63E 8E
, Day Mode to Siren output.
P53E
, Permanent Day Zone selection.
Temporary Day Zone selections will be
lost if the panel is powered down or reset,
but are not affected by arming/disarming
or entering program mode.