P R O G R A M M I N G
NESS D16 (V4.6) CONTROL PANEL - INSTALLER MANUAL
HANDOVER ZONES
Handover zones are delayed only if entry is made through an Entry Delay zone
first. If a Handover zone is triggered first, the zone behaves as an instant zone.
Normally, the “point of entry” zone should be Delay zone, with any other zones
in the entry path programmed as Handover zones.
PROGRAMMING SEQUENCE:
P42E [Zone No]E
turns the options ON
P42E [Zone No]E ON: The zone is a Handover zone
To deselect the option, select a different zone type in the DELAY GROUP.
P42E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
2E ON: Zone 2 is a Handover zone
NOTES:
• When a zone is selected for this type, it
is automatically deselected from any
other zone type in the DELAY GROUP
ENTRY DELAY2 ZONES
When an Entry Delay2 zone is triggered, it has entry delay as set by the Entry
Delay Time2 (P27E).
PROGRAMMING SEQUENCE:
P43E [Zone No]E
turns the options ON
P43E [Zone No]E ON: The zone is an Entry Delay2 zone
To deselect the option, select a different zone type in the DELAY GROUP.
P43E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
all OFF: No zones have Entry Delay2
NOTES:
• When a zone is selected for this type, it
is automatically deselected from any
other zone type in the DELAY GROUP
RESET LOCKOUT ZONES
All 16 zones and tamper input can be programmed to Lockout, i.e. cause the
RESET OUTPUT to sound only once whilst the panel is armed.
The RESET OUTPUT is then locked out for that alarmed zone until entering a
valid code has reset the panel.
PROGRAMMING SEQUENCE:
P44E [Zone No]E
toggles the options ON and OFF
P44E [Zone No]E OFF: The zone is not a Lockout zone
P44E [Zone No]E ON: The zone is a Lockout zone
P44E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
all ON: All zones are Lockout zones
NOTES:
• The SIREN output always locks out
•
0E
will turn all selections OFF
MEMORY E
will turn all selections ON
• RELATED OPTIONS:
P60E 4E
Tamper Reset Lockout
AREA PARTITIONING
See page 20
P45E, P46E
ASSIGNING USER CODES TO AREAS
See page 21
P47E - P50E
MONITOR ZONES
Monitor zones allow you to Arm selected zones while others are ignored.
Typically used for perimeter zones such as windows and doors while you are at
home. Example: Upstairs zones are Disarmed while downstairs zones are
Armed in Monitor mode.
PROGRAMMING SEQUENCE:
P51E [Zone No]E
toggles the options ON and OFF
P51E [Zone No]E OFF: The zone is not a Monitor zone
P51E [Zone No]E ON: The zone is a Monitor zone
P51E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
all OFF: No Monitor zones
NOTES:
• RELATED OPTIONS:
P63E
Monitor Mode output mapping
P64E 1E
2 second Monitor Mode alarm
P64E 3E
Monitor zones have Entry
Delay2