P R O G R A M M I N G
NESS D16 (V4.6) CONTROL PANEL - INSTALLER MANUAL
REPORT ZONE ALARMS
This option selects which zone inputs will send Alarm reports to the Central
Station.
PROGRAMMING SEQUENCE:
P74E 1E-16E
toggles the option ON and OFF
P74E 1E-16E OFF: Alarm reporting disabled for that zone
P74E 1E-16E ON: Alarm reporting enabled for that zone
P74E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
All zones report Alarms
NOTES:
•
0E
will turn all selections OFF
MEMORY E
will turn all selections ON
OPTION No
DESCRIPTION
1
2
3
4
5
6
7
8
9
10
11 12
13 14 15 16
P74E
Report zone alarms
P76E
Report zone restorals
P78E
Multiple zone alarms
P79E
Account No.2 zones
Zones
ON = Factory default setting
ON
ON ON ON ON ON ON
ON ON ON ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
REPORT ZONE RESTORALS
This option selects which zone inputs will send Restoral reports to the Central
Station. Only zones that have previously sent an Alarm will send a Restoral.
PROGRAMMING SEQUENCE:
P76E 1E-16E
toggles the option ON and OFF
P76E 1E-16E OFF: Restoral reporting disabled for that zone
P76E 1E-16E ON: Restoral reporting enabled for that zone
P76E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
All zones report Restorals
NOTES:
•
0E
will turn all selections OFF
MEMORY E
will turn all selections ON
• RELATED OPTIONS:
P82E 1E
Send Restoral immediately
P82E 2E
Send Restoral after siren time
P82E 3E
Send Restoral on Disarm & seal
P82E 4E
Send Restoral on Disarm always
REPORT MULTIPLE ZONE ALARMS
Zones selected for Multiple Zone Alarms will report each time the zone alarms
and without a restore being sent. The number of reports is a maximum of 15.
The number of alarms sent for each Multiple Zone Alarm can be reduced to 3
by using the swinger shutdown option P89E 4E.
Zones not selected report only once, until reset by an opening or a valid code.
PROGRAMMING SEQUENCE:
P78E 1E-16E
toggles the option ON and OFF
P78E 1E-16E OFF: Multiple Zone Alarms disabled for that zone
P78E 1E-16E ON: Multiple Zone Alarms enabled for that zone
P78E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
No zones report Multiple Alarms
NOTES:
• Only zones that have previously sent an
Alarm will send a Restoral
•
0E
will turn all selections OFF
MEMORY E
will turn all selections ON
• RELATED OPTIONS:
P89E 4E
Swinger shutdown
ACCOUNT NO.2 ZONES
Zones selected to be Account No.2 zones will report their Alarms, Restorals
and Excludes on Client code 2.
PROGRAMMING SEQUENCE:
P79E 1E-16E
toggles the option ON and OFF
P79E 1E-16E OFF: Multiple Zone Alarms disabled for that zone
P79E 1E-16E ON: Multiple Zone Alarms enabled for that zone
P79E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
All zones report Restorals
NOTES: