P R O G R A M M I N G
NESS D16 (V4.6) CONTROL PANEL - INSTALLER MANUAL
ENTRY BEEPS
The sonalert will beep during Entry Delay.
PROGRAMMING SEQUENCE:
P60E 1E
toggles the option ON and OFF
P60E 1E OFF: Entry Beeps OFF
P60E 1E ON: Entry Beeps ON
P60E 1E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
Entry Beeps ON
NOTES:
KEYSWITCH OPERATION
An externally fitted, normally open momentary keyswitch can be used to Arm,
Disarm or change the D16 to Monitor mode.
The keyswitch is wired to zone 8 (zone 8 is then no longer available as a
normal alarm input, but IS still available for use as a Radio Zone).
ARMED
ARMED
MONITOR
MONITOR
DISARM
DISARM
DISARM
PROGRAMMING SEQUENCE:
P60E 2E or 3E
toggles the option ON and OFF
P60E 2E & 3E OFF: No keyswitch operation. Zone 8 is a normal alarm input.
P60E 2E ON: Keyswitch cycles between Monitor and Disarm.
P60E 3E ON: Keyswitch cycles between Arm and Disarm.
P60E 2E & 3E ON: Keyswitch cycles between Arm, Monitor and Disarm.
P60E 2E, 3E
PROGRAM MODE LEVEL:
Installer, Remote by PC
FACTORY DEFAULT:
No keyswitch enabled
NOTES:
• The keyswitch always Arms Area1 only.
• The keyswitch always Disarms Area1
and
Area2.
• Momentary short circuit across resistor
to toggle panel modes.
• Open circuit resistor to trigger keyswitch
panic.
• Multiple keyswitches can be used. Wire
in parallel.
•
Zone Split.
If Zone 8 is converted to a
Keyswitch Input, then a 2K2 monitoring
resistor is always used and Zone Splitting
is not available on the Z8 input (no Zone8
or Zone16). Zone8 and Zone16 are still
available as RADIO ZONES however.
See: Zone Split, page 35
P60E 2E
is ON
P60E 3E
is ON
P60E 2E
is ON
P60E 3E
is ON
1E 2E 3E 4E 5E 6E 7E 8E
ON = Factory default setting.
Entr
y beeps
K
eysw Monitor/Disar
m
K
eysw/Ar
m/Disar
m
Tamper siren lockoutDuress to R
eset output
Auo Exclude zonesAuto KP display offDelay AREA1-2 outputs
OPTION No
DESCRIPTION
P60E
Various options
ON
ON
ON