Power, Ground, and Battery Cabling for Sites Equipped With
Customer–Supplied Site I/O Interface
– continued
DEC 2000
4-17
SC
t
300 BTS Hardware Installation, ATP and FRU Procedures
PRELIMINARY
Cables Needed
Table 4-14 provides the quantity and description of the cables needed.
Table 4-14: Cables Needed for Power, Earth Ground, and Battery Connections
Cable
Qty.
Part Number
Description
S
1–4
3087854C02
AC input cable, 14 AWG, 5 m, is designed for 88–260 VAC power
input.
U
1–4
3087854C04
DC input cable, 14 and 22 AWG, 5 m, is designed for 20 to 40 VDC
power input.
Y
1–4
Customer
Supplied
Ground cable, 6 -AWG, insulated copper wire. Requires one ring lug
connectors.
AC Input Cable Information
The pinout information for the AC input cable(s) (Cable S) is given in
Figure 4-9 and Table 4-15.
Figure 4-9: AC Input Cable Connector Information
A
B
C
SOCKET POSITION ON CABLE
CONNECTOR SHOWN
Table 4-15: AC Input Cable Information
Connector
Wire Color
Description
A
Black
Line
B
Green
Ground
C
White
Neutral
4