background image

 

 

USER'S GUIDE 

 

Vaisala HUMICAP

®

 Humidity and 

Temperature Transmitters 

HMW90 Series 

 

 

 

M211399EN-F 

Содержание HUMICAP HMW90 SERIES

Страница 1: ...USER S GUIDE Vaisala HUMICAP Humidity and Temperature Transmitters HMW90 Series M211399EN F...

Страница 2: ...hout prior written permission of the copyright holder Translated manuals and translated portions of multilingual documents are based on the original English versions In ambiguous cases the English ver...

Страница 3: ...13 Introduction to HMW90 Series 13 HMW90 Series Transmitters 14 Output Parameters Explained 15 Transmitter parts 16 CHAPTER 3 INSTALLATION 21 Configuration Before Installation 21 Configuration of Anal...

Страница 4: ...t Settings 47 Set Analog Output Mode 47 Set Analog Output Scaling 48 Set Output Clipping and Error Limit 49 Display Settings 50 Select Parameters to Display 50 Serial Line Output Commands 51 Start Mea...

Страница 5: ...PTER 6 TROUBLESHOOTING 75 Problem Situations 75 Error Messages 76 Error Messages on the Display 76 Error Messages on the Serial Line 76 View Currently Active Errors 76 View Error Table 77 Error State...

Страница 6: ...97 Out of Service 97 Operation Pressure Object 98 Present Value 98 Status Flags 98 Event State 98 Out of Service 98 Operation Altitude Object 99 Present Value 99 Units 99 Status Flags 99 Event State...

Страница 7: ...or HMW92 29 Figure 14 Wiring HMW93 30 Figure 15 Three Wire Wiring for HMW93 30 Figure 16 Wiring TMW92 31 Figure 17 Wiring TMW93 31 Figure 18 Three Wire Wiring for TMW93 31 Figure 19 Connecting a Commo...

Страница 8: ...t Properties 90 Table 20 Relative Humidity Object Properties 92 Table 21 Status Flags 93 Table 22 Reliability 93 Table 23 Event State 93 Table 24 Temperature Object Properties 94 Table 25 Status Flags...

Страница 9: ...transmitters Chapter 2 Product Overview introduces the features advantages and the product nomenclature Chapter 3 Installation provides you with information that is intended to help you install the H...

Страница 10: ...protocol implementations Updated configuration and wiring instructions Related Manuals Table 2 Related Manuals Manual Code Manual Name M211511EN HMW90 Series Quick Guide for Digital Output models M21...

Страница 11: ...arge ESD can cause immediate or latent damage to electronic circuits Vaisala products are adequately protected against ESD for their intended use It is possible to damage the product however by delive...

Страница 12: ...aracteristics Limits and methods of measurement Patent Notice The HMW90 series is protected by for example the following patents and their corresponding national rights Finnish patent 98861 French pat...

Страница 13: ...Internet pages for standard warranty terms and conditions www vaisala com warranty Please observe that any such warranty may not be valid in case of damage due to normal wear and tear exceptional oper...

Страница 14: ...ser s Guide _______________________________________________________________________ 12 ___________________________________________________________________ M211399EN F This page intentionally left blan...

Страница 15: ...re wall mount transmitters for building automation applications Transmitter models in the series share the following common features Detachable mounting base for easy installation and wiring Display v...

Страница 16: ...cover HMW93D Humidity and temperature transmitter with two voltage outputs 0 5 V or 0 10 V relay visible display TMW92 Temperature transmitter with one current output 4 20 mA display hidden under sli...

Страница 17: ...e current pressure Dewpoint Tdf C F Same as Td except when the dewpoint is below 0 C the transmitter outputs frostpoint Tf instead of dewpoint Dewpoint depression dTd C F Difference between ambient te...

Страница 18: ...211399EN F Transmitter parts 1201 004 Figure 2 Transmitter Parts Outside where 1 Locking screw for mounting base Not included M3 6 recommended 2 Adjustment trimmers 3 Service port 4 Window for display...

Страница 19: ...______________________________ Product Overview VAISALA________________________________________________________________________ 17 1201 005 Figure 3 Opening the Transmitter where 1 Push tab down with...

Страница 20: ...after the mounting base has been installed 6 Place for zip tie for cable strain relief 7 Transmitter body 8 DIP switches for common configuration options see section DIP Switches of Analog Output Mode...

Страница 21: ...behind 5 Label for RS 485 baud rate DIP switch settings 6 Orientation arrow should point up after the mounting base has been installed 7 Place for zip tie for cable strain relief 8 Transmitter body 9...

Страница 22: ...ser s Guide _______________________________________________________________________ 20 ___________________________________________________________________ M211399EN F This page intentionally left blan...

Страница 23: ...HMW95 Configuration of Analog Output Models You can configure analog output models of HMW90 series transmitters in two ways Using the DIP switches and rotary switch on the HMW93 and TMW93 on the comp...

Страница 24: ...els 0 10V 0 10V analog output both channels 4 Relay On Relay enabled Relay Off Relay disabled 5 Relay High Relay closed when measurement above setpoint Relay operation is linked to RH on HMW93 and T o...

Страница 25: ...at next power up Relay Configuration in DIP Mode NOTE Relay is included on HMW93 and TMW93 transmitters only When the transmitter is configured using DIP switches the functioning of the relay is confi...

Страница 26: ...n error state an active error is present Relay contacts are open when transmitter is powered off If you need to configure the relay for some other parameter or need additional configuration options se...

Страница 27: ...series have the following configuration interfaces DIP switches on the component board control operating protocol serial line settings and transmitter MAC address For instructions see DIP Switches of...

Страница 28: ...c Use non metric units on display and service port No effect on Modbus and BACnet Metric Use metric units on display and service port No effect on Modbus and BACnet 7 Not used 8 Not used NOTE If the s...

Страница 29: ...ight bit binary form with each numbered switch representing a single bit For example 1209 009 Figure 10 Example of Transmitter Addressing Addressing with BACnet Protocol BACnet MS TP MAC address range...

Страница 30: ...ources close to the discharge of the supply air ducts and in direct sunlight 1111 070 Figure 11 Selecting Transmitter Location Use the mounting holes to attach the mounting base securely Use at least...

Страница 31: ...nnect only de energized wires NOTE When wiring the transmitter make sure the electrical conduit or cable is not supplying air from outside the room into the transmitter Seal the cable opening if neces...

Страница 32: ...nded wiring for long cables 1111 068 Figure 14 Wiring HMW93 3 wire connection with Vs as common ground Maximum cable resistance is 2 5 24V supply 0 10 V output relay not used 1111 069 Figure 15 Three...

Страница 33: ...TMW93 Recommended wiring for long cables 1202 118 Figure 17 Wiring TMW93 3 wire connection with Vs as common ground Maximum cable resistance is 2 5 24V supply 0 10 V output relay not used 1202 119 Fig...

Страница 34: ...re connecting a common 24 VAC power supply to several transmitters make sure to connect the same terminal to Vs and Vs on all transmitters This will avoid a short circuit through the shared common lin...

Страница 35: ...re 20 Wiring HMW95 Connecting Several Transmitters on Same RS 485 Line HMW95 Set the RS 485 termination jumper to ON on the transmitter that is at the end of the line This terminates the line with a 1...

Страница 36: ...ser s Guide _______________________________________________________________________ 34 ___________________________________________________________________ M211399EN F This page intentionally left blan...

Страница 37: ...__________________________ 35 CHAPTER 4 OPERATION This chapter contains information that is needed to operate the HMW90 series transmitters Display Startup Screens When the transmitter is powered on i...

Страница 38: ...ment Screen Measurement screen shows the measured parameters and currently active indicators 1111 071 Figure 23 HMW93 Measurement Screen Normal Operation If there is a problem with measurement affecte...

Страница 39: ...MICAP Hand Held Humidity and Temperature Meter HM70 CAUTION The service port is not galvanically isolated from the rest of the transmitter electronics Connect only equipment with a floating power supp...

Страница 40: ...the USB service cable is not connected Disconnect the cable if you have already connected it 2 Insert the media that came with the cable or download the latest driver from www vaisala com 3 Execute th...

Страница 41: ...ation 3 Select the Serial settings category and check that the correct COM port is selected in the Serial line to connect to field Note You can check which port the USB cable is using with the Vaisala...

Страница 42: ...Guide _______________________________________________________________________ 40 ___________________________________________________________________ M211399EN F 0807 004 Figure 25 PuTTY Terminal Appli...

Страница 43: ...how list of currently available serial commands INTV 0 9999 s min h Set continuous output interval for R command PASS 9000 Access advanced serial commands R Start the continuous outputting RESET Reset...

Страница 44: ...tputs a listing of device information cr Example Device HMW93 SW version 1 00 0 0000 SNUM G5130008 HTM10 module information Software version 1 00 0 SNUM G5130007 Show Transmitter Firmware Version Use...

Страница 45: ...iled status for BACnet or Modbus protocol available on transmitter models with digital output Available switches are bacnet and modbus Example display detailed BACnet status status bacnet BACnet modul...

Страница 46: ...AL Active errors 0 MCI communication MCI Status NORMAL Analog output 1 AOUT1 Quantity x Input range 0 000 700 000 gr lb Output range 4 000 20 000 mA Output clipping 0 00 4 00 20 00 mA Valid output ran...

Страница 47: ...culated based on the measured values CALCS cr Example calcs RH Relative Humidity T Temperature Tdf Dew Frost point temperature Td Dew point temperature Tw Wetbulb temperature h Enthalpy x Mixing ratio...

Страница 48: ...le HELP cr Example shows basic serial commands advanced commands are not enabled here help CALCS ECHO ENV ERRT ERRS FORM HELP INTV PASS R RESET SDELAY SEND SNUM STATUS UNIT VERS Measurement Settings S...

Страница 49: ...m Unit Metric Analog Output Settings NOTE Commands for configuring analog outputs are not available on digital output models for example HMW95 Set Analog Output Mode Use the AMODE command to set the...

Страница 50: ...put channel 1 or 2 parameter Parameter that is output on the channel Available parameters are RH relative humidity T temperature Tdf dew frost point temperature Td dew point temperature Tw wetbulb tem...

Страница 51: ...put Mode on page 47 NOTE These settings have no effect on the measurements shown on the display The display will always show the currently measured values even outside the scaled output range as long...

Страница 52: ...Display Settings Select Parameters to Display Use the DSEL command to select the parameters that are displayed on the transmitter screen You can select parameters by abbreviation or select same param...

Страница 53: ...art Measurement Output Use the R command to start the continuous outputting of measurement values as an ASCII text string to the serial line The format of the measurement message is set with the FORM...

Страница 54: ...H T 23 12 C Set Output Interval Use the INTV command to change the output interval of the automatically repeating measurement messages The measurement messages are repeated in the RUN mode or after th...

Страница 55: ...s are used See Table 9 and Table 10 on page 54 and examples below Command to set default format form Example of default output RH 5 17 RH T 24 33 C RH 5 17 RH T 24 33 C RH 5 18 RH T 24 33 C RH 5 18 RH...

Страница 56: ...e return n Line feed String constant length 1 15 characters xxx ASCII code value decimal of a special character for example 027 for ESC Ux Shows the name of the measurement unit using x number of char...

Страница 57: ...nsmitters only Additional configuration options are available when relay functionality is configured via software The configuration is done using the RMODE and RSEL commands For examples see section R...

Страница 58: ...meter that controls the relay Available parameters are RH relative humidity T temperature Tdf dew frost point temperature Td dew point temperature Tw wetbulb temperature h enthalpy x mixing ratio a ab...

Страница 59: ...57 Relay Configuration Examples 1111 119 Figure 26 Relay Hi_Active in Custom Mode HMW93 1111 120 Figure 27 Relay Lo_active in Custom Mode HMW93 90 70 80 100 60 50 40 Relative Humidity Time 30 20 10 0...

Страница 60: ...oint humidity adjustment requires that the target condition is at least 50 of the currently measured value This prevents the user from making excessive corrections that are very unlikely to be needed...

Страница 61: ...the transmitter should be showing Example pass 9000 crh one 11 OK 2 point Adjustment of RH Measurement CRH LO HI x cr where LO Adjustment point at the dry end low RH HI Adjustment point at the wet end...

Страница 62: ...You can do a 1 point adjustment or clear the adjustment information from the HTM10 module Note that the factory adjustment will remain intact when user adjustment is cleared Show Current T Adjustment...

Страница 63: ...ample pass 9000 ct reset OK Enter Calibration and Adjustment Information Use the CTEXT command to store a text string that describes the calibration and or adjustment To enter a text string with space...

Страница 64: ...sted 1 or 2 value Voltage or current value to set the channel to Unit is determined according to output type V or mA The value you set may not be achievable by the transmitter Voltage output can go as...

Страница 65: ...lay test RTEST state cr where state State of the relay contacts Options are open open the relay contacts closed close the relay contacts Example close relay contacts pass 9000 rtest closed Relay test...

Страница 66: ...transmitter BACNET parameter_name parameter_value reinit cr where parameter_name Name of the BACnet parameter to change Available parameters are Instance BACnet instance number Unsigned 0 4194302 Nam...

Страница 67: ...et parameters bacnet Instance 6 00000006h Name NOT_SET Location Location Description Description Password 1234 MAX_MASTER 127 007Fh COV_Interval 0 Autobaud_Interval 10 Example change Location to 101 D...

Страница 68: ...ser s Guide _______________________________________________________________________ 66 ___________________________________________________________________ M211399EN F This page intentionally left blan...

Страница 69: ...nformation that is needed in basic maintenance of the HMW90 series Periodic Maintenance Cleaning The body of the transmitter can be cleaned by wiping with a moistened lint free cloth Do not use cleani...

Страница 70: ...69 1 point or 2 point adjustment using the service port See the following sections Adjustment Using an HM70 on page 70 Adjustment Using a PC on page 71 Replacement of the Humidity and Temperature Mod...

Страница 71: ...tments 1 To enter the adjustment screen open the slide and rotate the RH or T trimmer slightly during normal measurement If the trimmer is not centered you see the trimmer centering screen first Simpl...

Страница 72: ...djusts the measurement of the HMW90 transmitter to the same reading as the reference that is connected to the other port When the parameter being adjusted is RH both offset and gain are adjusted depen...

Страница 73: ...al line settings are 19200 N 8 1 3 Before changing the adjustment issue the following commands to see the transmitter s current adjustment information pass 9000 crh ct ctext cdate 4 Place the entire t...

Страница 74: ...HTM10 and TM10 Modules where 1 HTM10 module that includes a HUMICAP sensor for humidity measurement and a digital temperature sensor 2 TM10 module with a digital temperature sensor Replace the module...

Страница 75: ...he connector and damage it 1112 028 Figure 31 Replacing the HTM10 Module HMW93 3 Take the new module and align the pins to the connector on the transmitter s component board 4 Push down on the module...

Страница 76: ...ser s Guide _______________________________________________________________________ 74 ___________________________________________________________________ M211399EN F This page intentionally left blan...

Страница 77: ...g base pointing up Relay does not seem to be working as configured 1 Check DIP switch settings Is the relay configured using DIP switches and rotary switch or software Check that the rotary switch is...

Страница 78: ...0 05 HTM10 06 Problem with the HTM10 module 1 Check the module for damage 2 Check if the humidity sensor is missing or loose Note that the humidity sensor is not included on TMW type transmitters sinc...

Страница 79: ...ted 21 0 ERROR OFF HTM10 04 RH measurement 22 0 ERROR OFF HTM10 05 T measurement 23 0 ERROR OFF HTM10 01 Continuous communication failure 41 0 WARNING OFF HTM10 02 Single Communication failure 42 0 WA...

Страница 80: ...output the default error level is 5 5 V For 0 10 V output the default error level is 11 V For 4 20 mA output the default error level is 3 6 mA If all critical and error level errors are turned off by...

Страница 81: ...DIP Switches NOTE Factory reset functionality using DIP switches is present in transmitters with firmware version 1 0 3 or newer The firmware version is visible on the transmitter startup screen 1 Dis...

Страница 82: ...e DIP switches to the positions they were before 7 Reconnect the transmitter cover to the mounting base Check the startup screens to verify the configuration Reverting to Factory Settings Using Servic...

Страница 83: ...k vaisala com Provide at least the following supporting information Name and model of the product in question Serial number of the product Name and location of the installation site Name and contact i...

Страница 84: ...ser s Guide _______________________________________________________________________ 82 ___________________________________________________________________ M211399EN F This page intentionally left blan...

Страница 85: ...04 F 0 90 RH 1 7 RH 90 100 RH 2 5 RH Temperature range 5 10 C 40 55 C 23 50 F 104 131 F 0 90 RH 3 RH 90 100 RH 4 RH Stability in typical HVAC applications 0 5 RH year Humidity sensor Vaisala HUMICAP 1...

Страница 86: ...e 2 5 at 24V supply with 10 V output relay not used HMW95 Supply voltage 18 35 VDC 24 VAC 20 50 60 Hz Current consumption with termination Average 10 mA at 24 VDC Maximum 30 mA at 24 VDC Power consump...

Страница 87: ...color shade Spare Parts and Accessories Table 18 HMW90 Series Spare Parts and Accessories Description Order Code Humidity and Temperature Module for HMW92 HMW93 HMW95 and HMW90 HTM10SP Temperature Mo...

Страница 88: ...___________________ 86 ___________________________________________________________________ M211399EN F Dimensions in mm 1111 061 Figure 34 HMW90 Series Dimensions 1111 142 Figure 35 Dimensions of the...

Страница 89: ...MW90 Product Model Numbers HMW95 Applications Software Version 1 0 0 Firmware Version 1 0 0 0 BACnet Protocol Revision Version 1 Revision 4 BACnet Standardized Device Profile Annex L BACnet Operator W...

Страница 90: ...ut Multistate Value Notification Class Program Schedule Trend Log Data Link Layer Options BACnet Internet Protocol IP Annex J BACnet IP Annex J Foreign Device ISO 88023 Ethernet Clause 7 ANSI ATA 878...

Страница 91: ...n MS TP slaves and other devices Yes No Networking Options Router Clause 6 Annex H BACnet Tunneling Router over IP BACnet IP Broadcast Management Device BBMD Does the BBMD support registrations by For...

Страница 92: ..._Yxxxxxxx UV Nonvolatile Object_Type BACnetObjectType ENUMERATED N R 8 Device Object Fixed System_Status BACnetDeviceStatus ENUMERATED N R 0 Operational Volatile Vendor_Name Character String N R Vaisa...

Страница 93: ...ile Max_Info_Frames Unsigned N R O 1 Fixed Segmentation_Suppo rted BACnetSegmentation ENUMERATED N R 3 No segmentation Fixed APDU_Timeout Unsigned N R 3000 ms Fixed APDU_Retries Unsigned N R 0 Fixed D...

Страница 94: ...Object Properties Property Data type Application Type Writable Conformance Code Value or Initial Value Persistence Object_Identifier BACnetObjectIdentifier No R 00 00 00 02 hex Object Type 0 Instance...

Страница 95: ...eliability not 0 OVERRIDDEN FALSE Always FALSE OUT_OF_SERVICE FALSE Present Value may NOT be written via BACnet TRUE Present Value may be written via BACnet Reliability Table 22 Reliability State Caus...

Страница 96: ...s Nonvolatile Status_Flags BACnet Status Flags BIT STRING Yes when OoS R 0 FAULT FALSE Volatile Reliability BACnet Reliability ENUMERATED Yes when OoS O 0 NO FAULT DETECTED Volatile Event State BACnet...

Страница 97: ...y Table 26 Reliability State Cause 0 NO_FAULT_DETECTED 1 NO_SENSOR No contact to measurement module 2 OVER_RANGE T over 80 C 3 UNDER_RANGE T under 40 C 7 UNRELIABLE_OTHER Other measurement error Event...

Страница 98: ...f dry air Table 29 Calculated Humidity Object Properties Property Data type Application Type Writable Conformance Code Value or Initial Value Persistence Object_Identifier BACnetObjectIdentifier No R...

Страница 99: ..._SERVICE FALSE Present Value may NOT be written via BACnet TRUE Present Value may be written via BACnet Reliability Reliability of calculated humidity objects depends on reliability of RH measurement...

Страница 100: ...ACnet Object Type No 2 Analog Value Present Value Real Yes 1013 25 Description Character String No Operation Pressure Units BACnet Engineering Units No 133 hectopascals Status Flags BACnet Status Flag...

Страница 101: ...e Present Value Real Yes 0 0 Description Character String No Operating Altitude Units BACnet Engineering Units Yes 31 33 meters feet Status Flags BACnet Status Flags No 0 FAULT FALSE Event State BACne...

Страница 102: ...tiple B DS WPM B Data Sharing COV Unsolicited A DS COVU A Data Sharing COV Unsolicited B DS COVU B Alarm and Event Notification Internal B AE N I B Alarm and Event ACK B AE ACK B Alarm and Event Infor...

Страница 103: ...firmedPrivateTransfer ConfirmedTextMessage CreateObject DeleteObject DeviceCommunicationControl Disconnect Connection To Network Establish Connection To Network GetAlarmSummary GetEnrollmentSummary Ge...

Страница 104: ...ser s Guide _______________________________________________________________________ 102 __________________________________________________________________ M211399EN F This page intentionally left blan...

Страница 105: ...dress code is returned Function Codes Conformance class 0 function codes are enough to access the measurement data and configuration settings of HMW90 In addition some class 1 commands are also suppor...

Страница 106: ...for example 1xxxx 6xxxx or 7xxxx Subtract 1 to get address field values used in Modbus Protocol Data Unit PDU The register map is the same for all Modbus function codes For example function codes 03...

Страница 107: ...special values 0x7FFF 0x8000 or 0x8001 in a 16 bit integer register is ignored to avoid unintended result NOTE Some values may exceed the signed 16 bit range even in normal operation Please access su...

Страница 108: ...g out of range values is silently ignored NOTE Elevation is linked to pressure according to the following equation p 101325 1 2 25577 10 5 h 5 25588 where p is pressure in Pa and h is altitude above s...

Страница 109: ...MajorMinorVersion Software version for example 1 0 0 0x03 VendorUrl http www vaisala com 0x04 ProductName HMW90 0x80 SerialNumber Serial number e g H0710040 0x81 CalibrationDate Date of the last cali...

Страница 110: ...www vaisala com M211399EN...

Отзывы: