User's Guide _______________________________________________________________________
22 ___________________________________________________________________ M211399EN-F
DIP Switches of Analog Output Models
1111-066
Figure 6
DIP Switch Settings of Analog Output Models
DIP Position
Setting
1
Non-metric Non-metric units (°F).
Metric
Metric units (°C).
2
Td
Td (dewpoint) as humidity parameter on display and
analog output. Sets analog output scaling
to -20 ... +55 °C.
RH
RH (relative humidity) as humidity parameter on display
and analog output. Sets analog output scaling to
0 ... 100 %RH.
3
0...5V
0...5V analog output (both channels).
0...10V
0...10V analog output (both channels).
4
Relay On
Relay enabled.
Relay Off
Relay disabled.
5
Relay High Relay closed when measurement above setpoint.
Relay operation is linked to RH on HMW93, and T on
TMW93.
Relay Low Relay closed when measurement below setpoint.
6
Not used
7
Not used
8
Custom
Configuration through service port only.
DIP
Configuration by DIP switches only.
NOTE
DIP switch 2 does nothing on TMW92 and TMW93.
NOTE
If DIP switch 8 is set to
Custom
, the transmitter ignores all other DIP
switch settings. In custom mode the transmitter uses settings that are
configured in software using the service port.
No
n-M
etr
ic
Td 0..
.5V
Re
lay
On
Re
lay
Hig
h
Cu
sto
m
Me
tric RH
0..
.10
V
Re
lay
Of
f
Re
lay
Lo
w
DI
P
1 2 3 4 5 6 7 8
No
n-M
etr
ic
Td
Cu
sto
m
Me
tric RH
DI
P
1 2 3 4 5 6 7 8
HMW92/TMW92
HMW93/TMW93