8 - 15
MELSEC-Q/QnA
8. INCOMPLETE DERIVATIVE PID CONTROL INSTRUCTIONS
AND PROGRAM EXAMPLES
[PROGRAM EXAMPLE]
Sets the number of
loops to be used to 1.
Sets the number of loops
to be executed per scan
to 1.
Sets the operation
expression to forward
operation.
Sets the sampling cycle
to 1s.
Sets the proportional
constant to 1.
Sets the integral
constant to 3000s.
Sets the derivative
constant to 0s.
Sets the filter coefficient
to 0%.
Sets the MV lower limit
to 0.
Sets 0.
Sets the MV change rate
limit to 2000.
Sets the PV change rate
limit to 2000.
Sets the PID control data that are set in
D500 to D515.
Sets the initial
processing flag to 0.
Inputs the SV externally.
Saves the SV for manual to automatic
mode change processing.
PID operation start command
Sets the PV value from the Q64AD to
the I/O data area.
I/O data setting
Setting of
common data
of PID control
data
Setting of PID
control data for
loop 1
Sets the derivative gain
to 8.
Sets 0.
Sets 0.
Sets the Q62DA to output enable.
Sets the MV upper limit
to 2000.
Содержание Q Mode
Страница 1: ......
Страница 2: ......
Страница 14: ...A 12 MEMO ...
Страница 18: ...1 4 MELSEC Q QnA 1 GENERAL DESCRIPTION MEMO ...
Страница 48: ...4 14 MELSEC Q QnA 4 FUNCTIONS OF PID CONTROL MEMO ...
Страница 51: ...5 3 MELSEC Q QnA 5 PID CONTROL PROCEDURE MEMO ...
Страница 65: ...5 17 MELSEC Q QnA 5 PID CONTROL PROCEDURE MEMO ...
Страница 72: ...5 24 MELSEC Q QnA 5 PID CONTROL PROCEDURE MEMO ...
Страница 74: ...6 2 MELSEC Q QnA 6 PID CONTROL INSTRUCTIONS MEMO ...
Страница 120: ...9 28 MELSEC Q QnA 9 COMPLETE DERIVATIVE PID CONTROL INSTRUCTIONS AND PROGRAM EXAMPLES MEMO ...
Страница 125: ......
Страница 126: ......