9 - 17
MELSEC-Q/QnA
9. COMPLETE DERIVATIVE PID CONTROL INSTRUCTIONS AND
PROGRAM EXAMPLES
[PROGRAM EXAMPLE]
Sets the number of
loops to be used to 1.
Sets the operation
expression to forward
operation.
Sets the sampling
cycle to 1s.
Sets the proportional
constant to 1.
Sets the integral
constant to 3000s.
Sets the derivative
constant to 0s.
Sets the filter
coefficient to 0%.
Sets the MV lower limit
to 0.
Sets the MV upper limit
to 2000.
Sets the MV change
rate limit to 2000.
Sets the PV change
rate limit to 2000.
Sets the number of
loops to be executed
per scan to 1.
Sets the PID control data that are set in
D500 to D511.
Sets the initial
processing flag to 0.
Inputs the SV
externally.
Saves the SV for manual to automatic
mode change processing.
PID operation start command
I/O data setting
Sets the PV from the Q64AD to the I/O
data area.
Sets the manual mode.
Resets the devices
used for manual to
automatic mode
change processing.
Sets the MV
externally.
Processing in
manual mode
Sets the Q62DA to output enable.
Setting of common
data of PID control
data
Setting of PID control
data for loop 1
Содержание Q Mode
Страница 1: ......
Страница 2: ......
Страница 14: ...A 12 MEMO ...
Страница 18: ...1 4 MELSEC Q QnA 1 GENERAL DESCRIPTION MEMO ...
Страница 48: ...4 14 MELSEC Q QnA 4 FUNCTIONS OF PID CONTROL MEMO ...
Страница 51: ...5 3 MELSEC Q QnA 5 PID CONTROL PROCEDURE MEMO ...
Страница 65: ...5 17 MELSEC Q QnA 5 PID CONTROL PROCEDURE MEMO ...
Страница 72: ...5 24 MELSEC Q QnA 5 PID CONTROL PROCEDURE MEMO ...
Страница 74: ...6 2 MELSEC Q QnA 6 PID CONTROL INSTRUCTIONS MEMO ...
Страница 120: ...9 28 MELSEC Q QnA 9 COMPLETE DERIVATIVE PID CONTROL INSTRUCTIONS AND PROGRAM EXAMPLES MEMO ...
Страница 125: ......
Страница 126: ......