8. INCOMPLETE DERIVATIVE PID CONTROL INSTRUCTIONS
AND PROGRAM EXAMPLES
(9) The PID bumpless processing flag, SM794, is set to OFF. In the manual mode,
the SV is automatically rewritten to the PV when PID operation is performed.
Therefore, when the manual mode is returned to the automatic mode, the SV
must be rewritten to the one used in the automatic mode before switching to the
manual mode.
The SV is rewritten step-by-step 10 times as illustrated below:
SV value in manual mode
SV value in automatic mode
Manual to automatic
mode change command
1 s
10 s
1 s
1 s
1 s
The SV is rewritten using the operation method illustrated below:
= Incremental
value
Remainder
SV value in
manual mode
SV value in
automatice mode
-
10
The incremental value obtained with the formula above is added to SV every
second. The remainder is added in the first addition operation.