MELSEC-Q/QnA
5. PID CONTROL PROCEDURE
Table 5.1 PID Control Data List
Incomplete derivative
With PID limits
Without PID limits
Data
No.
Data Item
Description
Setting Range
User
Specification
Range
Setting Range
User
Specification
Range
7
MV Lower
limit (MVLL)
In the automatic mode, sets the
lower limit for the MV (manipulated
value) calculated in PID operation.
When the MV is less than the MV
lower limit, the MVLL is used as
the MV.
-50 to 2050
-50 to 2050
-32768 to
32767
-32768 to
32767
8
MV Upper
limit (MVHL)
In the automatic mode, sets the
upper limit for the MV calculated in
PID operation.
When the MV is greater than the
MV upper limit, the MVHL is used
as the MV.
-50 to 2050
-50 to 2050
-32768 to
32767
-32768 to
32767
9
MV change
rate limit
( MVL)
Sets the limit for variation between
the previous MV and present MV.
When the MV variation is greater
than the limit value, 1 is set for bit
1 (b1) of the alarm device.
Does not limit the MV variation.
(If the MV variation is greater than
the limit value, it is used
unchanged as the MV variation to
calculate the MV.)
0 to 2000
0 to 2000
-32768 to
32767
-32768 to
32767
10
PV change
rate limit
( PVL)
Sets the limit for variation between
the previous PV and present PV.
When the PV variation is greater
than the limit value, 1 is set for bit
0 (b0) of the alarm device.
Does not limit the PV variation.
(If the PV variation is greater than
the limit value, it is used
unchanged as the PV variation to
perform the PID operation.)
0 to 2000
0 to 2000
-32768 to
32767
-32768 to
32767
0.00 to 300.00
(Ideal value is
8.00)
0.00 to 300.00
(Ideal value is
8.00)
Data for
each
loop
11
Derivative
gain (K
D
)
Sets a time period (operation
delay) for derivative operation.
As the value is greater, the time
period decreases and operation
becomes closer to complete
derivative.
Infinite( )
If the setting
for K
D
exceeds
300.00
0 to 32767
(unit: 0.01)
Infinite( )
If the setting
for K
D
exceeds
300.00
0 to 32767
(unit: 0.01)
Содержание Q Mode
Страница 1: ......
Страница 2: ......
Страница 14: ...A 12 MEMO ...
Страница 18: ...1 4 MELSEC Q QnA 1 GENERAL DESCRIPTION MEMO ...
Страница 48: ...4 14 MELSEC Q QnA 4 FUNCTIONS OF PID CONTROL MEMO ...
Страница 51: ...5 3 MELSEC Q QnA 5 PID CONTROL PROCEDURE MEMO ...
Страница 65: ...5 17 MELSEC Q QnA 5 PID CONTROL PROCEDURE MEMO ...
Страница 72: ...5 24 MELSEC Q QnA 5 PID CONTROL PROCEDURE MEMO ...
Страница 74: ...6 2 MELSEC Q QnA 6 PID CONTROL INSTRUCTIONS MEMO ...
Страница 120: ...9 28 MELSEC Q QnA 9 COMPLETE DERIVATIVE PID CONTROL INSTRUCTIONS AND PROGRAM EXAMPLES MEMO ...
Страница 125: ......
Страница 126: ......