9 - 10
MELSEC-Q/QnA
9. COMPLETE DERIVATIVE PID CONTROL INSTRUCTIONS AND
PROGRAM EXAMPLES
[OPERATION ERRORS]
(1) An operation error will occur and the error flag (SM0) will be turned ON, and error
code will be stored in SD0, in the following cases.
• When the loop number designated by
n
does not exist.
(Error code: 4100)
• When
n
is outside the range 1 to 8. (Basic model QCPU)
(Error code: 4100)
• When
n
is outside the range 1 to 32. (High Performance model QCPU, Redundant
CPU, Universal model QCPU, QnACPU) (Error code: 4100)
• When the PID control data is outside the setting range.
(Error code: 4100)
• When the device range assigned to the PID control data area by
S
exceeds the
last device number of the applicable range.
(Error code: 4101)
• When the PIDINIT instruction has not been executed before execution of the
PIDPRMW instruction.
(Error code: 4103)