A - 1
•
SAFETY PRECAUTIONS
•
(You must read these cautions before using the product)
As for the use of the product, please carefully read this manual and the related manuals introduced later.
Also, please pay attention to safety adequately and manage the product correctly.
The safety cautions shown in this manual apply to the product only.
In this manual, the safety precautions are ranked as "DANGER" and "CAUTION".
!
DANGER
CAUTION
!
Indicates that incorrect handling may cause hazardous conditions,
resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions,
resulting in medium or slight personal injury or physical damage.
Note that the
!
CAUTION level may lead to a serious consequence according to the circumstances.
Always follow the instructions of both levels because they are important to personal safety.
Please store this manual in order to read whenever it is necessary. Also, always forward this manual to
the end users.
[Design Precautions]
!
DANGER
•
Install a safety circuit external to the programmable controller that keeps the entire system safe
even when there are problems with the external power supply or the programmable controller.
Otherwise, it may cause an output error or an operating error, resulting in an accident.
(1) Configure a circuit such as an emergency stop circuit and a protective circuit on the outside
of the programmable logic controller.
(2) When the programmable controller detects the following problems, it will stop calculation
and turn off all outputs.
• An overcurrent protective device or an overvoltage protective device in a power supply
module start running.
• A watchdog timer error or others is detected with self-checking function in the
programmable controller CPU.
All outputs may be turned on, when an error occurs in the part of I/O controlling or others
that the programmable controller CPU cannot detect. Build a fail safe circuit exterior to the
programmable controller to keep the entire system safe.
As for the fail safe circuit, refer to a CPU module User’s Manual.
•
Configure a circuit that turns on an external power supply when the main power of
programmable controller is turned on. If the external power supply is turned on first, it could
result in an output error or an operating error.
Содержание Q Mode
Страница 1: ......
Страница 2: ......
Страница 14: ...A 12 MEMO ...
Страница 18: ...1 4 MELSEC Q QnA 1 GENERAL DESCRIPTION MEMO ...
Страница 48: ...4 14 MELSEC Q QnA 4 FUNCTIONS OF PID CONTROL MEMO ...
Страница 51: ...5 3 MELSEC Q QnA 5 PID CONTROL PROCEDURE MEMO ...
Страница 65: ...5 17 MELSEC Q QnA 5 PID CONTROL PROCEDURE MEMO ...
Страница 72: ...5 24 MELSEC Q QnA 5 PID CONTROL PROCEDURE MEMO ...
Страница 74: ...6 2 MELSEC Q QnA 6 PID CONTROL INSTRUCTIONS MEMO ...
Страница 120: ...9 28 MELSEC Q QnA 9 COMPLETE DERIVATIVE PID CONTROL INSTRUCTIONS AND PROGRAM EXAMPLES MEMO ...
Страница 125: ......
Страница 126: ......