9 - 21
MELSEC-Q/QnA
9. COMPLETE DERIVATIVE PID CONTROL INSTRUCTIONS AND
PROGRAM EXAMPLES
[PROGRAM EXAMPLE]
Sets the number of loops to be
used to "2"
Sets the number of PID operation
execution loops per scan to "2"
Sets the operation expression
to forward operation
Sets the sampling cycle to
"1 s"
Sets the proportional constant
to "1"
Sets the integral constant to
"3000 s"
Sets the derivative constant
to "0 s"
Sets the filter coefficient to "0 %"
Sets the MV lower limit to "0"
Sets the MV upper limit to "2000"
Sets the MV change rate limit
to "2000"
Sets the PV change rate limit
to "2000"
Setting of common
data of PID control
data
Setting of PID
control data
for loop 1