8. INCOMPLETE DERIVATIVE PID CONTROL INSTRUCTIONS
AND PROGRAM EXAMPLES
[PROGRAM EXAMPLE]
Sets the number of loops to
be used to 2.
Sets the number of loops to
be executed per scan to 2.
Sets the operation expression
to forward operation.
Sets the sampling cycle to 1s.
Sets the proportional
constant to 1.
Sets the integral constant
to 3000s.
Sets the derivative constant
to 0s.
Sets the filter coefficient to
0%.
Sets the MV lower limit to 0.
Sets the MV upper limit to
2000.
Sets the MV change rate
limit to 2000.
Sets the PV change rate
limit to 2000.
Setting of
common
data of PID
control data
Setting of PID
control data
for loop 1
Sets 0.
Sets the derivative gain to 8.
Sets 0.
Sets 0.