APP - 3
MELSEC-Q/QnA
APPENDIX
Appendix 2 Anti-Reset Windup Measure
A reset windup is a problem that an integral element keeps adding a deviation beyond
a saturation limit. (It is also referred to as an integrator windup.)
When a reset windup occurs, integral operation must be stopped to enable immediate
response to the inversion of the deviation.
Since the anti-reset windup measure is taken in the PID operation instruction
(PIDCONT instruction and S.PIDCONT instruction) of the QCPU/QnACPU, it is
unnecessary to stop the integral operation.
Deviat
ion
Upper l
im
it
value
t
t
Without anti-reset windup measure: If deviation turns to decreasing direction,
response of MV delays. (Broken line)
With anti-reset windup measure: Integral function is stopped to prevent reset windup.
When integration of deviation decreases, integration
is executed.
MV