5 - 18
MELSEC-Q/QnA
5. PID CONTROL PROCEDURE
5.2 I/O Data
(1) The I/O data consists of input data, such as the SV (set value) and PV (process
value), which are set to execute PID operation, and output data, such as
operation results.
(2) The I/O data area is divided into the "data area where data are allocated loop-by-
loop" and "work area used by the system to perform PID operation".
Table 5.4 I/O Data List
Setting Range
QCPU
Data Name
Description
With PID limits
Without PID limits
Set value
SV
PID control target value
0 to 2000
-32768 to 32767
Process value PV
Feedback data from controlled system objective to
A/D converter module
-50 to 2050
-32768 to 32767
Automatic
manipulated
value
MV
The manipulated value calculated by PID
operation.
Output from the D/A converter module to the
controlled system.
-50 to 2050
-32768 to 32767
Process value
after filtering
PVf
Process value calculated using the operation
formula in POINT(1) in Section 3.1.2/ POINT(1) in
Section 3.2.2.
-50 to 2050
-32768 to 32767
Manual
manipulated
value
MV
MAN
In the manual control mode, the data output from
the D/A converter module is stored.
-50 to 2050
-32768 to 32767
Manual/
automatic
selection
MAN/
AUTO
Selects whether the output data to the D/A
converter module is shown as a manual
manipulated value or an automatic manipulated
value.
In manual control mode, the automatic
manipulated value remains unchanged.
0: Manual manipulated value
1: Automatic manipulated
value
0: Manual manipulated value
1: Automatic manipulated
value
Alarm ALARM
Used to determine if the change rate of the MV
(manipulated value) and the PV (process value) is
within or outside the allowable range.
Once set, the alarm data is retained until the user
resets it.
If the MV is outside the limit range, "1" is set for bit 1
(b1).
If the PV is outside the limit range, "1" is set for bit 0
(b0).
If the PV is outside
the limit range, '1'
is set for bit 0.
If the MV is outside
the limit range, '1'
is set for bit 1.
b15 to b2
b0
b1
If the PV is outside
the limit range, '1'
is set for bit 0.
If the MV is outside
the limit range, '1'
is set for bit 1.
b15 to b2
b0
b1
Содержание Q Mode
Страница 1: ......
Страница 2: ......
Страница 14: ...A 12 MEMO ...
Страница 18: ...1 4 MELSEC Q QnA 1 GENERAL DESCRIPTION MEMO ...
Страница 48: ...4 14 MELSEC Q QnA 4 FUNCTIONS OF PID CONTROL MEMO ...
Страница 51: ...5 3 MELSEC Q QnA 5 PID CONTROL PROCEDURE MEMO ...
Страница 65: ...5 17 MELSEC Q QnA 5 PID CONTROL PROCEDURE MEMO ...
Страница 72: ...5 24 MELSEC Q QnA 5 PID CONTROL PROCEDURE MEMO ...
Страница 74: ...6 2 MELSEC Q QnA 6 PID CONTROL INSTRUCTIONS MEMO ...
Страница 120: ...9 28 MELSEC Q QnA 9 COMPLETE DERIVATIVE PID CONTROL INSTRUCTIONS AND PROGRAM EXAMPLES MEMO ...
Страница 125: ......
Страница 126: ......