4 - 10
MELSEC-Q/QnA
4. FUNCTIONS OF PID CONTROL
4.3.2 MV upper/lower limit control function
(1) The MV upper/lower limit control function controls the upper or lower limit of the MV
calculated in the PID operation. This function is only effective in the automatic
mode. It cannot be executed in the manual mode.
(2) By setting the MV upper limit (MVHL) and the MV lower limit (MVLL), the MV
calculated in the PID operation can be controlled within the range between the
limits.
EV (deviation)
MV
AUTO
MV
AUTO
without limit
control
MVLL
(MV lower limit)
MVHL
(MV upper limit)
Fig. 4.6 Operation in Accordance with the MV Upper/Lower limit
(3) When the MV upper/lower limit control is used, the MV is controlled as illustrated
above.
A MVHL (MV upper limit) and MVLL (MV lower limit) takes on a value between -50
and 2050 or a user-defined value (except the QnACPU).
The following are the default settings:
• Upper limit ..................2000 (Or user-defined value)
• Lower limit ..................0 (Or user-defined value)
The value set for the upper limit must not be smaller than the value set for the lower
limit.
An error will occur if it is.
Содержание Q Mode
Страница 1: ......
Страница 2: ......
Страница 14: ...A 12 MEMO ...
Страница 18: ...1 4 MELSEC Q QnA 1 GENERAL DESCRIPTION MEMO ...
Страница 48: ...4 14 MELSEC Q QnA 4 FUNCTIONS OF PID CONTROL MEMO ...
Страница 51: ...5 3 MELSEC Q QnA 5 PID CONTROL PROCEDURE MEMO ...
Страница 65: ...5 17 MELSEC Q QnA 5 PID CONTROL PROCEDURE MEMO ...
Страница 72: ...5 24 MELSEC Q QnA 5 PID CONTROL PROCEDURE MEMO ...
Страница 74: ...6 2 MELSEC Q QnA 6 PID CONTROL INSTRUCTIONS MEMO ...
Страница 120: ...9 28 MELSEC Q QnA 9 COMPLETE DERIVATIVE PID CONTROL INSTRUCTIONS AND PROGRAM EXAMPLES MEMO ...
Страница 125: ......
Страница 126: ......