74
4 FUNCTIONS
4.16 2CH Conversion Mode Function
Compatible functions
The following functions can be used with the 2CH conversion mode. Settings used with other functions are invalid.
Setting procedure
1.
Set "Operation mode setting" to "2CH conversion mode".
[Navigation window]
[Parameter]
[Module Information]
Module model name
[Module Parameter]
[Basic
setting]
[Operation Mode Setting Function]
2.
Set the channel to be used with "Number of conversion enabled channels".
3.
Set the "Input type" and "Input range" of the channel to be used.
[Navigation window]
[Parameter]
[Module Information]
Module model name
[Module Parameter]
[Basic
setting]
[Range switching function]
Function
Input type/Range setting function
Voltage, current conversion function
Conversion method (Sampling processing)
Maximum value/Minimum value hold function
Number of conversion enabled
channels
Use enabled channel
Sampling cycle
0
None
1
CH1
1 ms
2
[CH1, CH5]
1 ms
3
[CH1, CH5], CH2
2 ms
4
[CH1, CH5], [CH2, CH6]
2 ms
5
[CH1, CH5], [CH2, CH6], CH3
3 ms
6
[CH1, CH5], [CH2, CH6], [CH3, CH7]
3 ms
7
[CH1, CH5], [CH2, CH6], [CH3, CH7], CH4
4 ms
8
[CH1, CH5], [CH2, CH6], [CH3, CH7], [CH4, CH8]
4 ms