4 FUNCTIONS
4.7 Alert Output Function
Setting procedure
1.
Set "Warning output setting (Rate alarm)" to "Enable".
[Navigation window]
[Parameter]
[Module Information]
Module model name
[Module Parameter]
[Application setting]
[Warning output function (Rate alarm)]
2.
Set the value to "Rate alarm change rate selection".
3.
Set values for "Rate alarm upper limit value" and "Rate alarm lower limit value".
Set values within the range satisfying the condition "Rate alarm upper limit value > Rate alarm lower limit
value".
If a value out of the range is set, a rate alarm upper/lower limit setting value inversion error (error code:
1BA
H) occurs.
4.
Set a value in "Rate alarm detection cycle setting".
Item
Setting range
Rate alarm change rate selection
0: Rate specification
1: Digital output value specification
Item
Setting range
Rate alarm upper limit value
-32768 to +32767
Rate alarm lower limit value
Item
Setting range
Rate alarm alert detection cycle setting
1 to 32000 (times)