Appendix 4 Buffer Memory Areas
151
A
CH1 Average processing specification
Set which processing is to be used, sampling processing or averaging processing.
Averaging processing consists of time average, count average, and moving average.
Setting a value other than the above causes an averaging process specification setting range error (error code: 191
H).
■
Buffer memory address
The following shows the buffer memory address of this area.
■
Enabling the setting
Turn off
→
on
→
off 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■
Default value
The default value is Sampling processing (0).
CH1 Time Average/Count Average/Moving Average
Configure the time (for averaging), count (for averaging), and moving average count for each channel where the averaging
processing is specified.
The following table lists the setting ranges.
Setting a value other than the above causes any of time average setting range error (error code: 192
H),
count average setting range error (error code: 193
H), moving count setting range error (error code:
194
H), and the conversion processing is executed with the setting before error.
■
Buffer memory address
The following shows the buffer memory address of this area.
■
Enabling the setting
Turn off
→
on
→
off 'Operating condition setting request' (Un\G70, b9) to enable the setting.
Setting value
Setting content
0
Sampling processing
1
Time average
2
Count average
3
Moving average
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH
Averaging process specification
501
701
901
1101
1301
1501
1701
1901
CH
Averaging process specification (In FX2N allocation mode function)
1081
1082
1083
1084
1085
1086
1087
1088
Setting content
Setting value
Time average
When the input type is current, and voltage: 4 to 10000 (ms)
When the input type is resistance temperature detector, and thermocouple: 160 to 10000 (ms)
Count average
4 to 10000 (times)
Moving average
2 to 1000 (times)
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH
Time Average/Count Average/Moving Average setting
502
702
902
1102
1302
1502
1702
1902
CH
Time average/Count average/Moving average setting (In
FX2N allocation mode function)
2
3
4
5
6
7
8
9