9 TROUBLESHOOTING
9.3 List of Error Codes
101
9
192
H
Time average setting range
error
■
When the input type is “current”, and “voltage”
When Time average is selected in CH
Average processing specification, a value other
than 4 to 10000 is set in CH
Time average/
Count average/Moving average setting.
■
When the input type is “current”, and “voltage”
Set a value of 4 to 10000 in CH
Time average/
Count average/Moving average setting.
■
When the input type is resistance temperature
detector, and thermocouple
When Time average is selected in CH
Average processing specification, a value other
than 160 to 10000 is set in CH
Time average/
Count average/Moving average setting.
■
When the input type is resistance temperature
detector, and thermocouple
Set a value of 160 to 10000 in CH
Time average/
Count average/Moving average setting.
193
H
Count average setting range
error
When Count average is set in CH
Average
processing specification, a value other than 4 to
10000 is set in CH
Time average/Count
average/Moving average setting.
Set a value of 4 to 10000 in CH
Time average/
Count average/Moving average setting again.
194
H
Moving average setting
range error
When the moving average is set in CH
Averaging processing specification, a value
other than 2 to 1000 is set in CH
Time
average/Count average/Moving average
setting.
Set a value of 2 to 1000 in CH
Time average/
Count average/Moving average setting again.
198
H
Celsius/Fahrenheit display
setting range error
A value other than 0 and 1 is set in CH
Celsius/Fahrenheit display setting.
Set 0 or 1 in CH
Celsius/Fahrenheit display setting
again.
1A0
H
Scaling enable/disable
setting range error
A value other than 0 and 1 is set in CH
Scaling enable/disable setting.
Set 0 or 1 in CH
Scaling enable/disable setting.
1A1
H
Scaling setting range error
A value other than -32000 to +32000 is set in
CH
Scaling lower limit value or CH
Scaling
upper limit value.
Set CH
Scaling lower limit value or CH
Scaling
upper limit value to -32000 to +32000 again.
1A2
H
Scaling upper/lower limit
value setting error
CH
Scaling lower limit value and CH
Scaling upper limit value are set as CH
Scaling lower limit value = CH
Scaling upper
limit value.
Set CH
Scaling lower limit value and CH
Scaling
upper limit value as CH
Scaling lower limit value
CH
Scaling upper limit value again.
1A5
H
Digital clipping enable/
disable setting range error
A value other than 0 and 1 is set in CH
Digital
clipping enable/disable setting.
Set CH
Digital clipping enable/disable setting to 0
or 1.
1AA
H
Maximum value reset request
setting range error
A value other than 0 and 1 is set in CH
Maximum value reset request.
Set 0 or 1 in CH
Maximum value reset request
again.
1AB
H
Minimum value reset request
setting range error
A value other than 0 and 1 is set in CH
Minimum value reset request.
Set 0 or 1 in CH
Minimum value reset request
again.
1B0
H
Alert output setting (Process
alarm) range error
A value other than 0 and 1 is set in CH
Alert
output setting (Process alarm).
Set 0 or 1 in CH
Alert output setting (Process
alarm).
1B
H
Process alarm upper lower
limit value setting range error
The values not satisfying the following condition
are set in CH
Process alarm upper upper limit
value to CH
Process alarm lower lower limit
value:
Upper upper limit value
≥
Upper lower limit
value
≥
Lower upper limit value
≥
Lower lower
limit value
indicates that the set values are as follows:
1: Process alarm lower lower limit value >
Process alarm lower upper limit value
2: Process alarm lower upper limit value >
Process alarm upper lower limit value
3: Process alarm upper lower limit value >
Process alarm upper upper limit value
Set CH
Process alarm upper upper limit value to
CH
Process alarm lower lower limit value so that
the values satisfy the following condition:
Upper upper limit value
≥
Upper lower limit value
≥
Lower upper limit value
≥
Lower lower limit value
1B8
H
Alert output setting (Rate
alarm) range error
A value other than 0 and 1 is set in CH
Alert
output setting (Rate alarm).
Set 0 or 1 in CH
Alert output setting (Rate alarm).
1B9
H
Rate alarm alert detection
cycle setting range error
A value other than 1 to 32000 is set in CH
Rate alarm alert detection cycle setting.
Set a value of 1 to 32000 in CH
Rate alarm alert
detection cycle setting.
1BA
H
Rate alarm upper/lower limit
setting value inversion error
CH
Rate alarm upper limit value and CH
Rate alarm lower limit value are set as Lower
limit value
≥
Upper limit value.
Set CH
Rate alarm upper limit value and CH
Rate alarm lower limit value as Lower limit value <
Upper limit value again.
1C0
H
Input signal error detection
setting range error
A value other than 0 to 4 is set in CH
Input
signal error detection setting.
Set CH
Input signal error detection setting value to
0 to 4.
Error code
Error name
Description and cause
Corrective action
Содержание MELSEC iQ-F
Страница 1: ...MELSEC iQ F FX5 User s Manual Analog Control Intelligent function module ...
Страница 2: ......
Страница 9: ...7 MEMO ...
Страница 181: ......