4 FUNCTIONS
4.14 Offset/Gain Initialization Function
71
4
Initial settings of the logging function
The following describes the initial setting procedure to use the logging function.
Setting procedure
1.
Set the “Input type”, and “Input range”.
[Navigation window]
[Parameter]
[Module Information]
Module model name
[Module Parameter]
[Basic
setting]
[Range switching function]
2.
Set "Logging enable/disable setting" to "Enable".
[Navigation window]
[Parameter]
[Module Information]
Module model name
[Module Parameter]
[Application setting]
[Logging function]
3.
Set the target data to be logged in "Logging data setting". Set either of "Digital output value" or "Digital operation value"
for each channel.
4.
Set the cycle to store the logging data to "Logging cycle setting value".
5.
Select a unit of the logging cycle setting value in "Logging cycle unit setting".
6.
Set a condition to generate a hold trigger in "Level trigger condition setting". To use 'CH1 Logging hold request'
(Un\G471), set "Disable". To use the level trigger, set either of Level trigger (Condition: Rise), Level trigger (Condition:
Fall), or Level trigger (Condition: Rise and fall).
7.
Set a number of the data points to be collected for the time period from the occurrence of a hold trigger to logging stop in
"Post-trigger logging points".
8.
Set a buffer memory address to be monitored for a level trigger to "Trigger data".
9.
Set a level where a level trigger operates for "Trigger setting value".
4.14
Offset/Gain Initialization Function
Offset/gain initialization
The offset and gain values are initialized to the factory default offset and gain values according to the set input type.
1.
Set the mode to the “Normal mode”.
2.
Set 'CH1 Input type/Range setting'(Un\G598) to 'CH8 Input type/Range setting' (Un\G1998) as 'Conversion disabled' and
turn off
→
on
→
off 'Operation condition setting request' (Un\G70, b9).
3.
Set "E20FH" to 'Offset/gain initialization enabled code' (Un\G305).
4.
Turn ON (1) 'Offset/gain initialization request' (Un\G70, b5).
Precautions
Channels for which the offset and gain have not been set are initialized with the current range.