102
9 TROUBLESHOOTING
9.3 List of Error Codes
1C1
H
Input signal error detection
setting value range error
A value other than 0 to 250 is set in CH
Input
signal error detection lower limit setting value or
CH
Input signal error detection upper limit
setting value.
Set CH
Input signal error detection lower limit
setting value or CH
Input signal error detection
upper limit setting value to 0 to 250.
1C5
H
Disconnection detection
enable/disable setting range
error
A value other than 0 and 1 is set in CH
Disconnection detection enable/disable setting.
Set 0 or 1 in CH
Disconnection detection enable/
disable setting.
1C6
H
Disconnection detection
enabled range setting range
error
CH
Input signal error detection setting is set in
Simple disconnection detection, and the Input
range is set in other than the following:
• 4 to 20 mA
• 1 to 5 V
For channels for simple disconnection detection
using the input signal error detection function, set
Input range setting to either of the following again.
• 4 to 20 mA
• 1 to 5 V
1D0
H
Logging enable/disable
setting range error
A value other than 0 and 1 is set in CH
Logging enable/disable setting.
Set 0 or 1 in CH
Logging enable/disable setting.
1D1
H
Logging cycle setting value
range error
A value out of the range is set in CH
Logging
cycle setting value and/or CH
Logging cycle
unit setting.
Set the value(s) within the range in one or both of
CH
Logging cycle setting value and CH
Logging
cycle unit setting.
1D2
H
Logging cycle setting disable
error
CH
Logging cycle setting value and CH
Logging cycle unit setting are set so that the set
logging cycle falls below the conversion cycle.
Set CH
Logging cycle setting value and CH
Logging cycle unit setting so that the logging cycle is
the conversion cycle of the object to be logged or
more.
1D3
H
Logging data setting range
error
A value other than 0 and 1 is set in CH
Logging data setting.
Set 0 or 1 in CH
Logging data setting.
1D4
H
Post-trigger logging points
setting range error
A value other than 1 to 10000 is set in CH
Post-trigger logging points.
Set a value of 1 to 10000 in CH
Post-trigger
logging points.
1D5
H
Level trigger condition setting
range error
A value other than 0 to 3 is set in CH
Level
trigger condition setting.
Set a value of 0 to 3 in CH
Level trigger condition
setting.
1D6
H
Trigger data setting range
error
A value other than 0 to 9999 is set in CH
Trigger data.
Set a value of 0 to 9999 in CH
Trigger data.
1D7
H
Logging hold request range
error
A value other than 0 and 1 is set in CH
Logging hold request.
Set 0 or 1 in CH
Logging hold request.
1E50H
Offset/gain setting channel
specification error
In the offset/gain setting, "1: Setting channel" is
set for both CH
Offset/gain setting mode
(offset specification) and CH
Offset/gain
setting mode (gain specification), or "0: Disable"
is set.
Correctly set CH
Offset/gain setting mode (offset
specification) and CH
Offset/gain setting mode
(gain specification).
1E51H
User range data invalid (CH
identification disabled)
An invalid value is set in the offset/gain setting.
The number of the channel in which this error
occurs cannot be identified.
Perform the offset/gain setting again for all channels
where the user range is set.
If the error occurs again, the possible cause is a
failure of the module. Please consult your local
Mitsubishi representative.
1E6
H
User range data invalid (CH
identification allowed)
An invalid value is set in CH
Offset/gain
setting.
Perform the offset/gain setting again for the
channels where the error has occurred.
If the error occurs again, the possible cause is a
failure of the module. Please consult your local
Mitsubishi representative.
1E7
H
Offset/gain value inversion
error
The offset value and gain value to be saved in
the flash memory are as follows:
Offset value
≥
Gain value
Perform the offset/gain setting again so that the
following condition is satisfied:
Offset value < Gain value
1E8
H
Offset/gain setting channel
range error
A value other than 0 and 1 is set in CH
Offset/
gain setting mode (offset specification) and
CH
Offset/gain setting mode (gain
specification).
Set CH
Offset/gain setting mode (offset
specification) and CH
Offset/gain setting mode
(gain specification) to 0 or 1.
1E9
H
Offset/gain setting out-of-
range error
The offset setting value and gain setting value
are as follows:
Offset value
≥
Gain value
Perform the offset/gain setting again so that the
following condition is satisfied:
Offset value < Gain value
1EB
H
Offset/gain channel change
error
The channel where disconnection has occurred
or channel where the conversion is disabled is
specified when Channel change request
(Un\G70, b11) has been turned on.
Check wiring for disconnection, or specify the
channel where the conversion is enabled.
1EC
H
Offset/gain setting for
specified channel out-of-
range error
The offset setting value or gain setting value for
the specified channel is out of the measuring
range when Channel change request (Un\G70,
b11) has been turned on.
Set a value within the measuring range as the offset
setting value or gain setting value for the specified
channel.
Error code
Error name
Description and cause
Corrective action
Содержание MELSEC iQ-F
Страница 1: ...MELSEC iQ F FX5 User s Manual Analog Control Intelligent function module ...
Страница 2: ......
Страница 9: ...7 MEMO ...
Страница 181: ......