158
APPX
Appendix 4 Buffer Memory Areas
CH1 Rate alarm lower limit value
Set a lower limit value of the change rate of digital operation values to detect a rate alarm.
For details on the alert output function, refer to the following.
■
Buffer memory address
The following shows the buffer memory address of this area.
■
Setting range
The possible setting range is from -32768 to +32767.
Unit of the setting value differs depending on the setting of ‘Rate alarm change rate selection’ (Un\G299).
■
Enabling the setting
Turn off
→
on
→
off 'Operating condition setting request' (Un\G70, b9) to enable the setting.
■
Default value
The default value is set to 0.
• When using the rate alarm, configure the 2-step settings for the rate alarm upper limit value and lower limit
value.
• A channel where the set values satisfy the condition "Rate alarm lower limit value
≥
Rate alarm upper limit
value" causes a rate alarm upper/lower limit setting value inversion error (error code: 1BA
H).
• Since the default value is 0, change the setting value.
CH1 Input signal error detection setting
Set a condition for detecting an input signal error.
For details on the input signal error detection function, refer to the following.
Page 46 Input Signal Error Detection Function
If a value other than the above is set, an input signal error detection setting range error (error code: 1C0
H) occurs.
When the 'CH1 Input type/range setting' (Un\G598) is set to resistance temperature detector or thermocouple, the setting of
'CH1 Input signal error detection setting' (Un\G528) is ignored.
■
Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH
Rate alarm lower limit value
526
726
926
1126
1326
1526
1726
1926
CH
Rate alarm lower limit value (In FX2N allocation mode
function)
1231
1232
1233
1234
1235
1236
1237
1238
Rate alarm change rate selection (Un\G299)
Unit
Rate specification (0)
0.1%
Digital output value specification (1)
digit
Setting value
Setting content
0
Disable
1
Upper and lower limit detection
2
Lower limit detection
3
Upper limit detection
4
Simple disconnection detection
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH
Input signal error detection setting
528
728
928
1128
1328
1528
1728
1928
CH
Input signal error detection setting (In FX2N allocation
mode function)
1151
1152
1153
1154
1155
1156
1157
1158