16
2 SPECIFICATIONS
2.3 Performance Specifications
Resistance temperature detector (RTD) input specifications
*1 Only 3-wire type resistance temperature detectors can be used.
Items
Specifications
Usable resistance temperature detector
Pt100, Ni100
Resolution
0.1
(0.2
)
Temperature measuring range
Pt100: -200 to +850
(-328 to +1562
)
Ni100: -60 to +250
(-76 to +482
)
Digital output value (16-bit signed binary)
Pt100: -2000 to +8500 (-3280 to +15620)
Ni100: -600 to +2500 (-760 to +4820)
Accuracy
Ambient temperature
25±5
Pt100:
±
0.8
Ni100:
±
0.4
Ambient temperature -20 to
+55
Pt100:
±
2.4
Ni100:
±
1.2