8 PROGRAMMING
8.1 Programming Procedure
93
8
Program example
Label settings
Classification
Device
Description
Device
Module label
FX5_8AD_1.bConversionCompletedFlag_D
Conversion completed flag
U1\G69, b14
FX5_8AD_1.bModuleREADY_D
Module READY
U1\G69, b0
FX5_8AD_1.bOperatingConditionSettingCompletedFlag_D
Operating condition setting completed flag
U1\G69, b9
FX5_8AD_1.stnMonitor_D[0].wDigitalOutputValue_D
Digital output value
U1\G400
FX5_8AD_1.stnMonitor_D[2].wDigitalOutputValue_D
Digital output value
U1\G800
FX5_8AD_1.stnMonitor_D[4].wDigitalOutputValue_D
Digital output value
U1\G1200
FX5_8AD_1.stnMonitor_D[6].wDigitalOutputValue_D
Digital output value
U1\G1600
FX5_8AD_1.uConversionCompletedFlag_D.0
Conversion completed flag
U1\G42, b0
FX5_8AD_1.uConversionCompletedFlag_D.2
Conversion completed flag
U1\G42, b2
FX5_8AD_1.uConversionCompletedFlag_D.4
Conversion completed flag
U1\G42, b4
FX5_8AD_1.uConversionCompletedFlag_D.6
Conversion completed flag
U1\G42, b6
FX5_8AD_1.stnControl_D[4].uMaxResetReq_D.0
Maximum value reset completed flag
U1\G1273, b0
FX5_8AD_1.stnControl_D[4].uMinResetReq_D.0
Minimum value reset completed flag
U1\G1274, b0
FX5_8AD_1.stnMonitor_D[4].uMaxResetCmpFlg_D.0
Maximum value reset completed flag
U1\G1222, b0
FX5_8AD_1.stnMonitor_D[4].uMinResetCmpFlg_D.0
Minimum value reset completed flag
U1\G1223, b0
FX5_8AD_1.stnMonitor_D[4].wMaxValue_D
Maximum value
U1\G1204
FX5_8AD_1.stnMonitor_D[4].wMinValue_D
Minimum value
U1\G1206
FX5_8AD_1.uWarningOutputFlagProcessAlarmLowerLimit_D.2
Warning output flag (Process alarm lower limit)
U1\G37, b2
FX5_8AD_1.uWarningOutputFlagProcessAlarmUpperLimit_D.2
Warning output flag (Process alarm upper limit)
U1\G36, b2
FX5_8AD_1.uWarningOutputFlagRateAlarmLowerLimit_D.0
Warning output flag (Rate alarm lower limit)
U1\G39, b0
FX5_8AD_1.uWarningOutputFlagRateAlarmUpperLimit_D.0
Warning output flag (Rate alarm upper limit)
U1\G38, b0
FX5_8AD_1.bErrorClearRequest_D
Error clear request
U1\G70, b15
FX5_8AD_1.bInputSignalErrorDetectionSignal_D
Input signal error detection signal
U1\G69, b12
FX5_8AD_1.uInputSignalErrorDetectionFlag_D.6
Input signal error detection flag
U1\G40, b6
FX5_8AD_1.uLatestAlarmCode_D
Latest alarm code
U1\G2
FX5_8AD_1.uDisconnectionDetectionFlag_D.0
Disconnection detection flag
U1\G41, b0
FX5_8AD_1.bErrorFlag_D
Error flag
U1\G69, b15
FX5_8AD_1.uLatestErrorCode_D
Latest error code
U1\G0
Labels to be
defined
Define global labels as shown below: