APPX
Appendix 4 Buffer Memory Areas
123
A
Warning output flag (Process alarm lower limit)
The lower limit alarm of the process alarm can be checked for each channel.
■
Buffer memory address
The following shows the buffer memory address of this area.
■
Alert output flag status
• If the limit specified by the process alarm lower lower limit value is equal to or exceeded, Alarm ON (1) is stored in 'Alert
output flag (Process alarm lower limit)' (Un\G37) of the corresponding channel.
• If an alert is detected even in one channel, of the channels where conversion is enabled and the alert output setting
(Process alarm) is enabled, 'Alert output signal' (Un\G69, b8) also turns on.
■
Clearing Alert output flag
• When the digital operation value becomes greater than the process alarm lower upper limit value, the flag is automatically
cleared.
• Turning off
→
on
→
off 'Operating condition setting request' (Un\G70, b9) allows the flag to be cleared.
Warning output flag (Process alarm upper limit/lower limit) [FX2N allocation mode]
When the FX2N allocation mode function is used, the upper/lower limit alarm of the process alarm can be checked.
■
Buffer memory address
The following shows the buffer memory address of this area.
■
Alert output flag status
• When the value is out of the range specified in the process alarm upper upper limit value or process alarm lower lower limit
value, Alarm ON (1) is stored in Alert output flag (Process alarm upper limit/lower limit) corresponding to each channel.
• If an alert is detected even in one channel, of the channels where conversion is enabled and the alert output setting
(Process alarm) is enabled, 'Alert output signal' (Un\G69, b8) also turns on.
■
Clearing Alert output flag
• When the digital operation value falls within the process alarm upper lower limit value or less, or process alarm lower upper
limit value or more, the flag is automatically cleared.
• Turning off
→
on
→
off 'Operating condition setting request' (Un\G70, b9) allows the flag to be cleared.
(1) 0: Normal, 1: Alarm ON
(2) The values of b8 to b15 are fixed to 0.
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
Warning output flag (Process alarm lower limit)
37
(1) 0: Normal, 1: Alarm ON
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
Alert output flag (Process alarm) (in FX2N allocation mode
function)
26
0
0
0
0
0
0
0
0
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b0
b1
b2
b3
b4
(1)
(2)
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b0
b1
b2
b3
b4
CH1
CH2 CH1
CH2
CH3
CH4 CH4
CH3
CH5
CH6 CH5
CH6
CH7
CH8 CH8
CH7
(1)
Lower limit
value
Upper limit
value
Lower limit
value
Lower limit
value
Lower limit
value
Lower limit
value
Lower limit
value
Lower limit
value
Lower limit
value
Upper limit
value
Upper limit
value
Upper limit
value
Upper limit
value
Upper limit
value
Upper limit
value
Upper limit
value
Содержание MELSEC iQ-F
Страница 1: ...MELSEC iQ F FX5 User s Manual Analog Control Intelligent function module ...
Страница 2: ......
Страница 9: ...7 MEMO ...
Страница 181: ......