APPX
Appendix 4 Buffer Memory Areas
125
A
Warning output flag (Rate alarm upper limit/lower limit) [FX2N allocation mode]
When the FX2N allocation mode function is used, the upper/lower limit alarm of the rate alarm can be checked.
■
Buffer memory address
The following shows the buffer memory address of this area.
■
Alert output flag status
• If the value is out of the range specified in the rate alarm upper limit value or the rate alarm lower limit value, Alarm ON (1)
is stored in Alert output flag (rate alarm) corresponding to each channel.
• If an alert is detected even in one channel, of the channels where conversion is enabled and the alert output setting
(Process alarm) is enabled, 'Alert output signal' (Un\G69, b8) also turns on.
■
Clearing Alert output flag
• When the change rate of the digital output value falls within the rate alarm upper limit value or less, or rate alarm lower limit
value or more, the flag is automatically cleared.
• Turning off
→
on
→
off 'Operating condition setting request' (Un\G70, b9) allows the flag to be cleared.
Input signal error detection flag
The status of an analog input value can be checked for each channel.
■
Buffer memory address
The following shows the buffer memory address of this area.
■
Input signal error detection flag status
• When an analog input value out of the range specified in Input signal error detection setting value is detected, Input signal
error detection flag corresponding to each channel of detection turns to Input signal error (1).
• When an error is detected in any channel where the conversion and the input signal error detection are enabled, 'Input
signal error detection signal' (Un\G69, b12) turns on.
(1) 0: Normal, 1: Alarm ON
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
Alert output flag (Rate alarm) (in FX2N allocation mode
function)
27
(1) 0: Normal, 1: Input signal error
(2) The values of b8 to b15 are fixed to 0.
Buffer memory name
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
Input signal error detection flag
40
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b0
b1
b2
b3
b4
CH1
CH2 CH1
CH2
CH3
CH4 CH4
CH3
CH5
CH6 CH5
CH6
CH7
CH8 CH8
CH7
(1)
Lower limit
value
Upper limit
value
Lower limit
value
Lower limit
value
Lower limit
value
Lower limit
value
Lower limit
value
Lower limit
value
Lower limit
value
Upper limit
value
Upper limit
value
Upper limit
value
Upper limit
value
Upper limit
value
Upper limit
value
Upper limit
value
0
0
0
0
0
0
0
0
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
b15 b14 b13 b12 b11 b10 b9
b8
b7
b6
b5
b0
b1
b2
b3
b4
(1)
(2)
Содержание MELSEC iQ-F
Страница 1: ...MELSEC iQ F FX5 User s Manual Analog Control Intelligent function module ...
Страница 2: ......
Страница 9: ...7 MEMO ...
Страница 181: ......