4 FUNCTIONS
4.13 Logging Function
65
4
■
Checking the trigger generation time
The trigger generation time can be checked with 'CH1 Trigger generation time' (Un\G444 to Un\G448).
Ex.
When 'CH1 Trigger generation time' (Un\G444 to Un\G448) is monitored
*1 These values assume that a trigger is generated at 10:35 and 40.628 seconds on Monday, January 30th, 2017.
Item
Storage contents
Storage example
First two digits of the year/Last two digits of the
year
Stored in BCD code.
2017H
Month/Day
0130H
Hour/Minute
1035H
Second
40H
Day of the week
One of the following values is stored in BCD code.
• Sunday: 00H
• Monday: 01H
• Tuesday: 02H
• Wednesday: 03H
• Thursday: 04H
• Friday: 05H
• Saturday: 06H
01H
Millisecond (higher-order digits)/Millisecond
(lower-order digits)
Stored in BCD code.
0628H
b15
b8 b7
b0
to
to
First two digits of the year
Last two digits of the year
Month
Day
Hour
Minute
Second
Day of the week
Millisecond (higher-order digits)
Millisecond (lower-order digits)
'CH1 Trigger generation time (First/Last two digits of the year)' (Un\G444)
'CH1 Trigger generation time (Month/Day)' (Un\G445)
'CH1 Trigger generation time (Hour/Minute)' (Un\G446)
'CH1 Trigger generation time (Second/Day of the week)' (Un\G447)
'CH1 Trigger generation time (Millisecond)' (Un\G448)
Содержание MELSEC iQ-F
Страница 1: ...MELSEC iQ F FX5 User s Manual Analog Control Intelligent function module ...
Страница 2: ......
Страница 9: ...7 MEMO ...
Страница 181: ......