background image

R3Y-PA16

P. 1 / 2

EM-8962 Rev.1

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check
the contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.

■ 

PACKAGE INCLUDES:

Totalized pulse input module ..................................... (1)

■ 

MODEL NO.

Check that model No. described on the specification label is
exactly what you ordered.

■ 

INSTRUCTION MANUAL

This manual describes necessary points of caution when you
use this product, including installation, connection and basic
maintenance procedures.

POINTS OF CAUTION

■ 

CONFORMITY WITH EC DIRECTIVES

• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices and connected wires may
affect the protection level of this unit when it is integrated in
a panel system.  The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure CE conformity.

■ 

HOT INSERTION/REMOVAL OF MODULES

Removing or replacing modules does not affect other modules
on the same backplane.  It is possible to replace them without
removing the power supply.  However, replacing multiple
modules at once may greatly change line voltage levels.  We
recommend that you replace them one by one.

■ 

ENVIRONMENT

• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing with sufficient ventila-
tion.
• Do not install the unit where it is subjected to continuous
vibration.  Do not subject the unit to physical impact.
• Environmental temperature must be within -10 to +55

°

C

(14 to 131

°

F) with relative humidity within 30 to 90% RH in

order to ensure adequate life span and operation.

■ 

WIRING

• Do not install cables (power supply, input and output) close
to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises
are present.  Do not install them in the same duct.

■ 

AND ....

• The unit is designed to function as soon as power is
supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data sheet.

INSTRUCTION  MANUAL

MODEL

R3Y-PA16

TOTALIZED PULSE INPUT MODULE

(Pi 16 points)

COMPONENT IDENTIFICATION

INSTALLATION

Use the Installation Base (model: R3-BSx).

9

10
11
12
13
14
15
16

1
2
3
4
5
6
7
8

B

20

A

20

B

1

A

1

RUN LED

ERR LED

Status Indicator LED

Input Connector

FRONT VIEW

• Pin Assignment

SIDE VIEW

SW3

ON

4
3
2
1

Count
Reset

Set the Count Reset SW to OFF to start counting.

STATUS INDICATOR LED

RUN indicator

: Bi-color (red/green) LED;

Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.

ERR indicator

: Bi-color (red/green) LED;

Red with the excitation abnormality;
Green in normal operating conditions.

Input status indicator

: Red LED; turns on with the inputs

supplied.

Отзывы: