FX2N-16CCL-M CC-Link System Master Block
Data Link Procedure 8
8-11
8.5.2
T-shaped branch communication specification list
The table below shows the communication specification in T-shaped branch connection.
For communication specification not shown in the table below, refer to Section 4.4.
Table 8.2:
Item
Specification
Remarks
Transmission speed
625kbps
156kbps
10, 5 and 2.5 Mbps are not available.
Maximum main line
length
100m
500m
The value indicates the cable length
between terminal resistors.
The cable length of T-shaped branch lines
(branch length) is not included.
Maximum branch line
length
8m
The value indicates the cable length per
branch line.
Total branch line
length
50m
200m
The value indicates the total length of all
branch lines.
Maximum number of
modules connected to
branch line
6 modules/branch line
The number of connected modules
conforms to the CC-Link specification.
Connection cable
Dedicated CC-Link cable
(Examples: FANC-SB, CSFV-SLAB,
100ZCLK-SB-20AWGX3C)
• Dedicated high-performance CC-Link
cables (example: FANC-SBH) are not
available.
• Cables produced by different
manufacturers are not available at the
same time.
(For manufacturers, refer to brochures.)
Terminal resistor
(connection method)
Connect a terminal resistor (110
Ω
) packed
together with master module.
For the connection method, refer to Section
8.4.
T-shaped branch
terminal block/
connector
• Terminal block: Commercial one
• Connector:
Connector for FA sensor NECA4202
(IEC947-5-2) or its equivalent is
recommended.
(NECA: THE JAPAN ELECTRIC
CONTROL EQUIPMENT INDUSTRY
ASSOCIATION Standards)
• When wiring cables to the main line, strip
as little of the insulation as possible.
Maximum main line
length, T-shaped
branch interval and
cable length between
modules
Dedicated CC-Link cable (with terminal resistor of 110
Ω
)
Transmission
speed
Maximum
main line
length
T-shaped
branch
interval
Cable length between
remote stations*1
Cable length between
master station and
adjacent station*2
625kbps
100m
No limit
30 cm or more
1 m or more
156kbps
500m
Master
station
Terminal
resistor
Terminal
resistor
R
R
R
R
R
R
R
R
R
R
R
R
R
R
*2
*2
*2
*2
*1
*1
*1
*1
*1
*1
*1
*1
Maximum main line length (excluding branch line length)
: Indicates a remote I/O station or remote device station.
R
(Branch line length: 8 m or less)
(Branch line length: 8 m or less)
*1
R
*1
*1
T-shaped branch interval
Содержание FX2N-16CCL-M
Страница 4: ...FX2N 16CCL M CC Link System Master Block ii ...
Страница 6: ...FX2N 16CCL M CC Link System Master Block iv ...
Страница 34: ...FX2N 16CCL M CC Link System Master Block System Configuration 3 3 14 MEMO ...
Страница 66: ...FX2N 16CCL M CC Link System Master Block Specification 4 4 32 MEMO ...
Страница 144: ...FX2N 16CCL M CC Link System Master Block Programming 9 9 16 MEMO ...
Страница 172: ...FX2N 16CCL M CC Link System Master Block Communication in Compound System 12 12 10 MEMO ...
Страница 192: ...FX2N 16CCL M CC Link System Master Block Appendix 14 14 4 MEMO ...
Страница 193: ......