FX2N-16CCL-M CC-Link System Master Block
Troubleshooting 13
13-6
From the
previous page
From the
previous page
Is station No. switch
correctly set (without
overlapping another
station)?
Is L RUN LED lit?
Is SD LED lit (flashing)?
Y
Is SD LED lit (flashing)?
Is transmission speed
correctly set?
Set transmission speed
correctly.
Turn off power, then turn it on
again. Or turn on reset switch.
Are communication
cables correctly
wired?*1
N
N
Correct wiring of
communication cables.
N
Y
Corresponding
module is
defective.
Is station No. switch
correctly set (without
overlapping another
station)?
Y
Corresponding module is
defective.
(transmission speed switch)
Corresponding module is
defective.
(station No. switch)
Y
Corresponding module is
defective.
(station No. switch)
Turn off power, then turn it on
again. Or turn on reset switch.
N
Set station No.
correctly.
Turn off power, then turn it on
again. Or turn on reset switch.
N
Set station No.
correctly.
Completed
*1 Check for short circuit, inverse connection and wire breakage. Check the terminal resistors, the FG connection,
the total extension distance and the station-to-station distance.
N
Y
Y
N
Y
From the
previous page
Содержание FX2N-16CCL-M
Страница 4: ...FX2N 16CCL M CC Link System Master Block ii ...
Страница 6: ...FX2N 16CCL M CC Link System Master Block iv ...
Страница 34: ...FX2N 16CCL M CC Link System Master Block System Configuration 3 3 14 MEMO ...
Страница 66: ...FX2N 16CCL M CC Link System Master Block Specification 4 4 32 MEMO ...
Страница 144: ...FX2N 16CCL M CC Link System Master Block Programming 9 9 16 MEMO ...
Страница 172: ...FX2N 16CCL M CC Link System Master Block Communication in Compound System 12 12 10 MEMO ...
Страница 192: ...FX2N 16CCL M CC Link System Master Block Appendix 14 14 4 MEMO ...
Страница 193: ......