8) Read normal completion of data link startup by EEPROM parameters: BFM#A
H
b8
Indicates the normal completion status of the data link startup request by the write request
for data link startup by EEPROM parameters (BFM#A
H
b8).
a) When the write request for data link startup by EEPROM parameters (BFM#A
H
b8) is set
to ON, the contents of the EEPROM parameters are checked. When the contents are
normal, the system automatically starts data link.
b) When data link startup is normally completed, the read normal completion of data link
startup by EEPROM parameters (BFM#A
H
b8) turns ON.
c) When the write request for data link startup by EEPROM parameters (BFM#A
H
b8) is set
to OFF, the read normal completion of data link star tup by EEPROM parameters
(BFM#A
H
b8) turns OFF.
9) Read abnormal completion of data link startup by EEPROM parameters: BFM#A
H
b9
Indicates the abnormal completion status of the data link startup request by the write
request for data link startup by EEPROM parameters (BFM#A
H
b8).
a) When the write request for data link startup by EEPROM parameters (BFM#A
H
b8) is set
to ON, the contents of the EEPROM parameters are checked. When the contents are
abnormal, the read abnormal completion of data link startup by EEPROM parameters
(BFM#A
H
b9) turns ON.
b) The read parameter setting status (BFM#A
H
b2) turns ON, the error code is stored in the
buffer memory for the parameter status in host station (SW0068).
c) When the write request for data link startup by EEPROM parameters (BFM#A
H
b8) is set
to OFF, the read abnormal completion of data link startup by EEPROM parameters
(BFM#A
H
b9) turns OFF.
Read normal completion of data link startup
by EEPROM parameters
(BFM#A
H
b8)
Read parameter setting status
(BFM#A
H
b2)
Parameter status in host station
(SW0068)
Write request for data link startup by
EEPROM parameters
(BFM#A
H
b8)
OFF
0
Startup
processing
Read abnormal completion of data link
startup by EEPROM parameters
(BFM#A
H
b9)
Read parameter setting status
(BFM#A
H
b2)
Parameter status in host station
(SW0068)
Write request for data link startup by
EEPROM parameters
(BFM#A
H
b8)
OFF
0
Error code
Startup
processing
Содержание FX2N-16CCL-M
Страница 4: ...FX2N 16CCL M CC Link System Master Block ii ...
Страница 6: ...FX2N 16CCL M CC Link System Master Block iv ...
Страница 34: ...FX2N 16CCL M CC Link System Master Block System Configuration 3 3 14 MEMO ...
Страница 66: ...FX2N 16CCL M CC Link System Master Block Specification 4 4 32 MEMO ...
Страница 144: ...FX2N 16CCL M CC Link System Master Block Programming 9 9 16 MEMO ...
Страница 172: ...FX2N 16CCL M CC Link System Master Block Communication in Compound System 12 12 10 MEMO ...
Страница 192: ...FX2N 16CCL M CC Link System Master Block Appendix 14 14 4 MEMO ...
Страница 193: ......