System Configuration 3
3-1
3.
System Configuration
This chapter describes the system configuration for the CC-link in which an FX Series PLC
functions as the master station.
3.1
Total Configuration
Up to 7 remote I/O stations and up to 8 remote device stations can be connected to one FX
Series PLC functioning as the master station. (Each of the numbers "7" and "8" excludes the
master station.)
However, the following conditions must be satisfied in connection:
When using a FX
3U
PLC
1) Total number of I/O points
2)
Total number of points of the remote I/O st
ation
3)
Maximum number of input/output poi
nts
4) Connection of remote device stations (up to 8 stations)
Up to 8 remote device stations can be connected without regard to the number of points shown in
1), 2) and 3) above.
Number of I/O points in PLC (including vacant
numbers and extension I/O points)
points
Number of points occupied by FX
2N
-16CCL-M
8 points
Total number of points occupied by other
special extension PLCs
points
[Total]
points
≤
256
32
×
Number of remote I/O stations
points
[Total]
points
≤
224
Total number of I/O points 1)
points
Total number of points of the remote I/O
station 2)
points
[Total]
points
≤
384
Number of remote device stations occupying 1
station
1 station
×
modules
stations
Number of remote device stations occupying 2
stations
2 stations
×
modules
stations
Number of remote device stations occupying 3
stations
3 stations
×
modules
stations
Number of remote device stations occupying 4
stations
4 stations
×
modules
stations
[Grand total]
stations
≤
8
FX2N-16CCL-M CC-Link System Master Block
Содержание FX2N-16CCL-M
Страница 4: ...FX2N 16CCL M CC Link System Master Block ii ...
Страница 6: ...FX2N 16CCL M CC Link System Master Block iv ...
Страница 34: ...FX2N 16CCL M CC Link System Master Block System Configuration 3 3 14 MEMO ...
Страница 66: ...FX2N 16CCL M CC Link System Master Block Specification 4 4 32 MEMO ...
Страница 144: ...FX2N 16CCL M CC Link System Master Block Programming 9 9 16 MEMO ...
Страница 172: ...FX2N 16CCL M CC Link System Master Block Communication in Compound System 12 12 10 MEMO ...
Страница 192: ...FX2N 16CCL M CC Link System Master Block Appendix 14 14 4 MEMO ...
Страница 193: ......