FX2N-16CCL-M CC-Link System Master Block
Specification 4
4-4
4.4.1
Maximum transmission distance
This section describes the relationship between the transmission speed and the maximum
transmission distance.
1) In the system consisting of only remote I/O stations and remote device stations
*1 Cable length between remote I/O or remote device stations
*2 Cable length between the master station and an adjacent station
Dedicated CC-Link cable (requiring terminal resistor of 110
Ω
)
Dedicated high-performance CC-Link cable (requiring terminal resistor of 130
Ω
)
Table 4.2:
Transmission
speed
Cable length between stations
Maximum
transmission
distance
*1
*2
156kbps
30 cm or more
1 m or more
1200m
625kbps
600m
2.5Mbps
200m
5Mbps
30 cm to 59 cm *
110m
60 cm or more
150m
10Mbps
30 cm to 59 cm *
50m
60 cm to 99 cm *
80m
1 m or more
100m
Table 4.3:
Transmission
speed
Cable length between stations
Maximum
transmission
distance
*1
*2
156kbps
30 cm or more
1 m or more
1200m
625kbps
900m
2.5Mbps
400m
5Mbps
160m
10Mbps
100m
Remote I/O station
or remote device
station
Master station
Remote I/O station
or remote device
station
Remote I/O station
or remote device
station
Remote I/O station
or remote device
station
*2
*2
*1
*1
Maximum transmission distance
Содержание FX2N-16CCL-M
Страница 4: ...FX2N 16CCL M CC Link System Master Block ii ...
Страница 6: ...FX2N 16CCL M CC Link System Master Block iv ...
Страница 34: ...FX2N 16CCL M CC Link System Master Block System Configuration 3 3 14 MEMO ...
Страница 66: ...FX2N 16CCL M CC Link System Master Block Specification 4 4 32 MEMO ...
Страница 144: ...FX2N 16CCL M CC Link System Master Block Programming 9 9 16 MEMO ...
Страница 172: ...FX2N 16CCL M CC Link System Master Block Communication in Compound System 12 12 10 MEMO ...
Страница 192: ...FX2N 16CCL M CC Link System Master Block Appendix 14 14 4 MEMO ...
Страница 193: ......