FX2N-16CCL-M CC-Link System Master Block
Functions 5
5-24
5.12.3
Temporary error invalid station specification procedure
This section describes the procedure to execute the temporary error invalid station function.
Point
1) Even if the request for temporary error invalid station is executed for a faulty
station, the error information is not cleared.
The temporary error invalid station specification function is effective only to errors
which occur after the specification.
2) The request for temporary error invalid and the request for cancel of temporary
error invalid station are not effective to stations which are specified as error
invalid stations by parameter.
Select whether two or more stations are to be specified as temporary error
invalid stations (SW0003).
(00: Two or more stations, 01 to 15: One station)
Set to ON the request for temporary error invalid station (SB0004).
Turn off the power of temporary error invalid stations, and replace them.
Turn on the power of temporary error invalid stations.
Set to ON the request for cancel of temporary error invalid station (SB0005).
Содержание FX2N-16CCL-M
Страница 4: ...FX2N 16CCL M CC Link System Master Block ii ...
Страница 6: ...FX2N 16CCL M CC Link System Master Block iv ...
Страница 34: ...FX2N 16CCL M CC Link System Master Block System Configuration 3 3 14 MEMO ...
Страница 66: ...FX2N 16CCL M CC Link System Master Block Specification 4 4 32 MEMO ...
Страница 144: ...FX2N 16CCL M CC Link System Master Block Programming 9 9 16 MEMO ...
Страница 172: ...FX2N 16CCL M CC Link System Master Block Communication in Compound System 12 12 10 MEMO ...
Страница 192: ...FX2N 16CCL M CC Link System Master Block Appendix 14 14 4 MEMO ...
Страница 193: ......