FX2N-16CCL-M CC-Link System Master Block
Parameter Setting 7
7-9
2) Operation based on parameters registered in the EEPROM
This program operates the system based on parameter set values registered in the
EEPROM.
When the parameter set values have to be changed due to a change or addition to the
system, it is necessary to re-register parameters to the EEPROM.
Refer to 1) for the parameter registration method.
M40
SET
M1
SET
K1
D100
H0668
K0
FROM
M8002
Module
error
M20
M35
Initial pulse
Module
ready
M1
When data link startup by
EEPROM parameters is
completed abnormally
BFM#A
H
→
M35 to M20
M0
M0
PLS
M48
SET
M48
RST
M1
RST
M48
RST
M1
RST
When data link startup by
EEPROM parameters is
completed normally
M28
M29
M8000
RUN monitor
Refresh command
K1
K4M20
HA
K0
FROM
K1
K4M40
HA
K0
TO
M8000
RUN monitor
M55 to M40
→
BFM#A
H
Содержание FX2N-16CCL-M
Страница 4: ...FX2N 16CCL M CC Link System Master Block ii ...
Страница 6: ...FX2N 16CCL M CC Link System Master Block iv ...
Страница 34: ...FX2N 16CCL M CC Link System Master Block System Configuration 3 3 14 MEMO ...
Страница 66: ...FX2N 16CCL M CC Link System Master Block Specification 4 4 32 MEMO ...
Страница 144: ...FX2N 16CCL M CC Link System Master Block Programming 9 9 16 MEMO ...
Страница 172: ...FX2N 16CCL M CC Link System Master Block Communication in Compound System 12 12 10 MEMO ...
Страница 192: ...FX2N 16CCL M CC Link System Master Block Appendix 14 14 4 MEMO ...
Страница 193: ......