FX2N-16CCL-M CC-Link System Master Block
System Configuration 3
3-7
3.4
Number of Occupied Stations and Station numbers as well as Number of
Modules and Number of Stations
This section describes the relationship between the number of occupied stations and the
station as well as between the number of modules and the number of stations.
1) Number of occupied stations
The number of stations occupied by each remote I/O station or remote device station is
shown in Table 3.2.
2) Station number
When the number of stations occupied by every station module is 1, assign consecutive
section numbers beginning with 1 (1, 2, 3, ...).
If there is a station module occupying 2 or more stations, the number of occupied stations
should be taken into account when the station are assigned.
3) Number of modules and number of stations
The number of modules indicates the number of physical modules.
The number of stations indicates the number of stations occupied by all modules as
described in 1).
In the example of system configuration shown in 2), the number of modules is 5 and the
number of stations is 9.
Table 3.2:
Module
Number of occupied stations
Remote I/O station (module with 16 or 32 points)
1
Remote device station
FX
2N
-32CCL
1 to 4 (selectable)
AJ65BT-64AD
2
AJ65BT-64DAV
2
AJ65BT-64DAI
2
AJ65BT-D62
AJ65BT-D62D(S1)
4
A852GOT
2 or 4
Master
station
Station No. 1
Remote I/O
station (occupies
1 station)
Station No. 3
Remote
device station
FX
2N
-32CCL
(occupies 4
stations)
Station No. 4
Remote I/O
station (occupies
1 station)
Station No. 8
Remote
device station
FX
2N
-32CCL
(occupies 1
station)
Station No. 9
Remote
device station
(occupies 2
stations)
Station
No. 1
Station
No. 2
Station
No. 3
Station
No. 4
Station
No. 5
Station
No. 6
Station
No. 7
Station
No. 8
Station
No. 9
Содержание FX2N-16CCL-M
Страница 4: ...FX2N 16CCL M CC Link System Master Block ii ...
Страница 6: ...FX2N 16CCL M CC Link System Master Block iv ...
Страница 34: ...FX2N 16CCL M CC Link System Master Block System Configuration 3 3 14 MEMO ...
Страница 66: ...FX2N 16CCL M CC Link System Master Block Specification 4 4 32 MEMO ...
Страница 144: ...FX2N 16CCL M CC Link System Master Block Programming 9 9 16 MEMO ...
Страница 172: ...FX2N 16CCL M CC Link System Master Block Communication in Compound System 12 12 10 MEMO ...
Страница 192: ...FX2N 16CCL M CC Link System Master Block Appendix 14 14 4 MEMO ...
Страница 193: ......