FX2N-16CCL-M CC-Link System Master Block
Data Link Procedure 8
8-2
WIRING PRECAUTIONS
• Perform Class D grounding (100
Ω
or less) with a wire of 2 mm
2
or more to the grounding
terminal in the PLC main unit. However, never perform common grounding with a high
voltage system.
• Do not bundle control cables and communication cables with the main circuit and power
cables. Keep control cables and communication cables at least 100 mm away from the main
circuit and power cables.
Otherwise, electric noise may cause a malfunction.
PLC
Another
equipment
PLC
Another
equipment
PLC
Another
equipment
Common grounding
(allowed)
Common grounding
(not allowed)
Dedicated grounding
(best)
Содержание FX2N-16CCL-M
Страница 4: ...FX2N 16CCL M CC Link System Master Block ii ...
Страница 6: ...FX2N 16CCL M CC Link System Master Block iv ...
Страница 34: ...FX2N 16CCL M CC Link System Master Block System Configuration 3 3 14 MEMO ...
Страница 66: ...FX2N 16CCL M CC Link System Master Block Specification 4 4 32 MEMO ...
Страница 144: ...FX2N 16CCL M CC Link System Master Block Programming 9 9 16 MEMO ...
Страница 172: ...FX2N 16CCL M CC Link System Master Block Communication in Compound System 12 12 10 MEMO ...
Страница 192: ...FX2N 16CCL M CC Link System Master Block Appendix 14 14 4 MEMO ...
Страница 193: ......